5Ć8
swapping out modules, determine whether the module
being tested is the only module that is not working
correctly. If more than one module is not working correctly,
the problem most likely lies in the remote I/O system.
Refer to the instruction manual for the M/N 57C416
Remote I/O Communications module for more information.
If the problem does not lie in the remote I/O system, it
probably involves the remote rack.
To test the remote rack, systematically swap out the
module being tested and the slave Remote I/O module. If
the problem persists, take all of the modules except the
slave Remote I/O module and the module being tested out
of the rack. If the problem is now corrected, one of the
other modules in the rack is malfunctioning. ReĆconnect
the other modules one at a time until the problem
reappears. If the problem appears to be neither in the
remote I/O system nor in the remote rack replace the
backplane.