4Ć2
Processor in the rack is a M/N 57C430A or M/N 57C431, the
operating system(s) will be loaded at 9600 baud. At 9600 baud, it will
require approximately two minutes to load each operating system to
Processors in the rack. Although they are similar, the operating
systems for the 6010/6011 and 7010 Processor are different. If there
are 6010/6011 and 7010 Processors mixed in the same rack, loading
the operating systems will take approximately twice as long as it
would if there were only one type of Processor in the rack.
Follow the directions below to load the operating system(s) for all
Processor modules in the local rack at one time. You can then load
the operating system(s) to all racks on all networks in the system.
Note: If you load an operating system into a Processor(s) that
already contains one, the new operating system will write over
the existing operating system, and any tasks in the Processor(s)
will be deleted.
1. If you have not already done so, turn on the personal computer
and run the AutoMax Executive by typing
AUTOMAX2
or
AUTOMAX3
2. Turn on power to the rack. You will note that the leftmost
Processor module in the rack displays the letters L" and O"
(reading top to bottom). This code prompts you to Load the
Operating system. Because Processor modules have onĆboard
battery backup, you will need to reĆload the operating system
only when enhancements become available, when you change
the password for the rack using the PWOS.EXE utility or when a
Processor module in the rack is replaced.
3. If you have not already done so, connect the personal computer
to the leftmost processor in the rack, following the directions
in 4.4.
4. Enter a <CR> at the initial screen. If you are using AutoMax
Version 2, select F10 for Load Operating System". If you are
using AutoMax Version 3, select Load Operating System" from
the Commands menu. Note that you will see the message Local
OS invalid Ć Direct connection only" before you load the
operating system for the first time. The AutoMax Executive
software will load the operating system onto all Processor
modules in the local rack at the normal baud rate. The AutoMax
Executive will display on the screen the portion (%) of the
operating system that has been loaded.
5. When installation begins, the code L" O" will disappear from the
two sevenĆsegment LEDs on the leftmost Processor module. The
LEDs should be blank. If any error codes appear on the LEDs of
the leftmost Processor, the loading was not successful. Repeat
step 4 above.
6. You can now load the operating system to other racks in the
system connected to the local rack (the rack to which your
personal computer is connected) through 57C404A Network
Communication modules. For any network containing 57C404
Network Communication modules, you must connect directly to
each rack on the network to load the operating system (see steps
1Ć5 above).
Komentáře k této Příručce