Chapter 8
Creating Data Entry Screens
8–9
32 Bit Floating Point
Important: 32 bit floating point is an option on a DTAM Plus with PLC-5
DF1, DH485, or RIO protocol selected.
See Appendix D for DTAM Micro Floating Point format.
The screen for a 32 Bit Floating Point format is shown below.
Format Selection Description
Register Number The PLC address to be monitored.
Minimum Register Value The minimum data value of the controller address being monitored.
Maximum Register Value The maximum data value of the controller address being monitored.
Minimum Entry Value The minimum data value to be entered. When this value is
entered the minimum register value is entered to the defined
controller address.
Maximum Entry Value The maximum data value to be entered. When this value is entered
the maximum register value is entered to the defined controller
address. The range defined by the minimum entry value and the
maximum entry value is proportionally scaled to the range of the
minimum and maximum register values. If both ranges are equal
then the scaling ratio is 1:1.
Low User Input Limit The minimum entry value that an operator may enter. This value
must be within the range of the data format selected. If a value lower
than this is entered, the DTAM will display an “Input Error” screen
displaying the minimum and maximum entry limits.
High User Input Limit The maximum entry value that an operator may enter. This value
must be within the range of the data format selected. If a value
higher than this is entered, the DTAM will display an “Input Error”
screen displaying the minimum and maximum entry limits.
Default Value This parameter defines a default value that is displayed at the
entry address of the display. An entry of Z defines no default.
NONE appears in the window when Z is entered.