Chapter 7
Creating Data Display Screens
78
32 Bit Floating Point
Important: 32 bit floating point is supported on the DTAM Plus if PLC-5
DF1, DH485, or Remote I/O protocol has been selected.
See Appendix D for DTAM Micro floating point format.
The screen for a 32 Bit Floating Point format is shown below.
Format Selection Description
Register Number The PLC address to be monitored.
Minimum Register Value The minimum data value of the PLC address.
Maximum Register Value The maximum data value of the PLC address.
Minimum Displayed Value The minimum data value to be displayed. This value is displayed
when the data in the PLC address is equal to the minimum register
value.
Maximum Displayed Value The maximum data value to be displayed. This value is displayed
when the data in the PLC address is equal to the maximum register
value.
The range defined by the Minimum Displayed Value and the
Maximum Displayed Value is proportionally scaled to the range of
the minimum and maximum register values. If both ranges are equal
then the scaling ratio is 1:1.