104 Rockwell Automation Publication 520COM-UM001B-EN-E - March 2013
Chapter 7 Using Multi-Drive Mode
Drive 2 Control Routine
0
5
(End)
Copy File
Source
Dest
Length
Drive_Input_Image[7]
Drive_2_Feedback
1
COP
12
Copy File
Source
Dest
Length
Drive_2_Reference
Drive_Output_Image[5]
1
COP
15
Return from Subroutine
RET
Drive_Input_Image[6].0 Drive_2_Status_Ready
This section takes the data from the input area and moves it to specic tags (Logic Status bits and Feedback) for use
elsewhere in the ladder program.
This section takes the data from specic tags (Logic Command bits and Reference) and moves them to the output
image area for transmission to the scanner.
Drive 2 parameters are accessed by adding 18432 decimal (4800 hex) to the desired parameter number. For example,
to access parameter P109 an Instance of 18541 (18432 + 109) is used.
1
Drive_Input_Image[6].1 Drive_2_Status_Active
2
Drive_Input_Image[6].3 Drive_2_Status_Forward
3
Drive_Input_Image[6].7 Drive_2_Status_Faulted
4
Drive_Input_Image[6].8 Drive_2_Status_At_Reference
6
Drive_2_Command_Stop Drive_Output_Image[4].0
7
Drive_2_Command_Start Drive_Output_Image[4].1
8
Drive_2_Command_Jog Drive_Output_Image[4].2
9
Drive_2_Command_Clear_Faults Drive_Output_Image[4].3
10
Drive_2_Command_Forward Drive_Output_Image[4].4
13
Perform_Parameter_Read_2
EN
DN
ER
11
Drive_2_Command_Forward Drive_Output_Image[4].5
Message
Message Control Parameter_RD_Message_2
MSG
14
Perform_Parameter_Write_2
EN
DN
ER
Message
Message Control Parameter_WR_Message_2
MSG
Explicit Messaging Example
Drive 2 Control Subroutine