Rockwell Automation Publication 750-PM001J-EN-P - October 2014 491
Using DeviceLogix Appendix C
Figure 89 - Two Input Four Position Selector Switch Logic Map
Discrete Inputs in the Drive are used for Inputs 1 and Input 2. Output A, B, C,
and D are linked to DeviceLogix Scratchpad Registers. This allows further
flexibility to modify the values of these outputs.
The resulting output can be linked to a parameter and used in supporting drive
applications, such as configuring multiple preset speeds and point to point
positioning. In this example, it controls Preset Speed 1.
Parameter Configuration
The following parameters are configured for this example:
Port Parameter
No.
Parameter Value Description
14.1 DLX Out 01 Port 0:Preset Speed 1
14.33 DLX DIP 1 Port 4: Dig In Status.Input 1 Digital input 1 from Selector
Switch
14.34 DLX DIP 2 Port 4: Dig In Status.Input 2 Digital input 2 from Selector
Switch
14.17 DLX In 01 Port 14: DLX Real SP1 Output A
14.18 DLX In 02 Port 14: DLX Real SP2 Output B
14.19 DLX In 03 Port 14: DLX Real SP3 Output C
14.20 DLX In 04 Port 14: DLX Real SP4 Output D
14.54 DLX Real SP1 75.00 Output A Preset Speed
14.55 DLX Real SP2 85.00 Output B Preset Speed
14.56 DLX Real SP3 95.00 Output C Preset Speed
14.57 DLX Real SP4 105.00 Output D Preset Speed
0.571 Preset Speed 1 varies Resulting output from Selector
Switch
Digital Input 1
DLX
DIP 1
Digital Input 2
DLX
DIP 2
DLX
Out 1
00
01
10
11
Output A
Output B
Output C
Output D
Komentáře k této Příručce