Rockwell Automation Publication 750-PM001J-EN-P - October 2014 481
Application Notes Appendix B
g. Click the Communication tab. See Figure 86.
Figure 86 - Message Configuration Screen - Communication Tab
h. In the Path field, enter the drive name to configure the communication
path of the message instruction to that drive.
In this case, the drive name in the Logix I/O tree is “_DriveName.
i. The [Elapsed Life] data returns with a floating point (Real) data
format. The raw data is already in hours. See Figure 87
.
Figure 87 - Predictive Main Group Parameters (Port 11)
6. Use a Compute (CPT) instruction with a subtraction expression to
calculate the [Remaining Life] parameter. See Figure 88
.
Figure 88 - Compute (CPT) Instructions