Rockwell-automation 20B PowerFlex 70, PowerFlex 700 Reference Manual Uživatelský manuál Strana 100

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 214
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 99
Efficiency
100 Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013
Efficiency The following chart shows typical efficiency for PWM variable frequency drives,
regardless of size. Drives are most efficient at full load and full speed.
Fan Curve When torque performance (see page 201) is set to Fan/Pump, the relationship
between frequency and voltage is shown in the following figure. The fan/pump
curve generates voltage that is a function of the stator frequency squared up to the
motor nameplate frequency. Above base frequency voltage is a linear function of
frequency. At low speed the fan curve can be offset by the run boost parameter to
provide extra starting torque if needed. No extra parameters are needed for fan/
pump curve.
The pattern matches the speed vs. load characteristics of a centrifugal fan or
pump and optimizes the drive output to those characteristics.
Fan See Fan Curve above.
10 20 30 40 50 60 70 80 90 100
% Speed/% Load
% Efficiency
vs. Speed
vs. Load
75
80
85
90
95
100
Maximum Voltage
Maximum
Frequency
Base Voltage
(Nameplate)
Base Frequency
(Nameplate)
Run Boost
Zobrazit stránku 99
1 2 ... 95 96 97 98 99 100 101 102 103 104 105 ... 213 214

Komentáře k této Příručce

Žádné komentáře