Publication 2092-RM001A-EN-P — March 2005
2-30 Command Reference
Group 4 Parameters
[Pr – 4.00] Current Scale
[Pr – 4.01] Positive Internal Current Limit
[Pr – 4.02] Negative Internal Current Limit
[Pr – 4.03] Positive External Current Limit
[Pr – 4.04] Negative External Current Limit
Range: 0 to 1000
Default: 333
Units: % of rated continuous current/V *10
Operating Mode:
Analog Current Command, Dual Current Command
Ultraware Name:
Current Limits: Positive Internal
Range: 0 to 500
Default: 500
Units: % of motor rated continuous current
Operating Mode: All
Ultraware Name: Current Limits: Negative Internal
Range: 0 to 500
Default: 500
Units: % of motor rated continuous current
Operating Mode: All
Ultraware Name: Current Limits: Positive External
Range: 0 to 500
Default: 100
Units: % of motor rated continuous current
Operating Mode: All
Ultraware Name: Current Limits: Negative External
Range: 0 to 500
Default: 100
Units: % of motor rated continuous current
Operating Mode: All