66 Rockwell Automation Publication 750COM-UM005B-EN-P - June 2014
Appendix B Option Module Parameters
About Parameter Numbers
Each parameter set is independently and consecutively numbered.
How Parameters Are
Organized
The Device Parameters and Host Parameters are separately displayed in a
Numbered List view order.
Device Parameters
Configuration Tool Numbering Scheme
HIM
Connected Components Workbench software
DriveExplorer software
DriveExecutive software
Device parameters begin with parameter 01
(Device Parameter 01 - [Port Number]).
Host parameters begin with parameter 33
(Host Parameter 33 - [Comm Flt Action]).
IMPORTANT
The 20-750-BNETIP Option Module does not support all Host parameters
that appear in the configuration tool. A list of supported Host parameters
is provided later in this appendix.
Parameter
No. Name and Description Details
01 [Port Number]
Displays the drive port into which the option
module is installed. Typically, this is Port 4, 5, or 6.
Minimum: 4
Maximum: 6
Type: Read Only
02 [Net Addr Src]
Displays the source from which the option
module’s node address is taken.
Values: 0 = Parameters
1 = Default
Type: Read Only
03 [Reset Module]
No action if set to ‘0’ (Ready). Resets the option
module if set to ‘1’ (Reset Module). Restores the
option module to its factory default settings if set
to ‘2’ (Set Defaults). This parameter is a command.
It will be reset to ‘0’ (Ready) after the command
has been performed.
When performing a Set Defaults, the drive may
detect a conflict. If this occurs, the drive will not
allow a Set Defaults action. You must resolve the
conflict before attempting a Set Defaults action for
the option module.
Default: 0 = Ready
Values
: 0 = Ready
1 = Reset Module
2 = Set Default
Type: Read/Write
Reset Required: No
ATTENTION: Risk of injury or equipment damage exists. If the option
module is transmitting I/O that controls the drive, the drive can fault
when you reset the option module. Determine how your drive will
respond before resetting the option module.