8 ArmorBlock MaXum 4 Input / 4 Output Module with 8 Connectors, Series B
Publication 1792D-IN050A-EN-P - February 2001
Refer to the table below for the word/bit definitions.
The DeviceNet Network uses advanced network technology,
producer/consumer communication, to increase network
functionality and throughput. Visit our web site at
http://www.ab.com/networks
for producer/consumer technology
information and updates.
Bit 07 06 05 04 03020100
Produced
Byte 0
ISC-D ISC-C ISC-B ISC-A I3 I2 I1 I0
Produced
Byte 1
OFLT3 OFLT2 OFLT1 OFLT0 OW-D OW-C OW-B OW-A
Produced
Byte 2
RSVD OPWR RSVD RSVD RSVD RSVD RSVD RSVD
Consumes
Byte 0
RSVD RSVD RSVD RSVD O3 O2 O1 O0
Where: ISC=Input Short Circuit in Sensor Source Voltage; I = Input; OFLT = Output fault;
OW= Off Wire; RSVD = Reserved; OPWR= Output Power (Auxiliary Power); O = Output
Byte Bit Description
Produces 0 00-03
04-07
Input Status bits: When the bit is set (1), the input is on.
Bit 00 = to input 0, bit 01 = to input 1, bit 02 = to input 2, bit
03 = to input 3.
Input short circuit fault: ISC-A = a short circuit for connector A
Input short circuit fault: ISC-B = a short circuit for connector B
Input short circuit fault: ISC-C = a short circuit for connector C
Input short circuit fault: ISC-D = a short circuit for connector D
Produces 1 00-03
04-07
Input off wire fault: OW-A = an off-wire fault for connector A
Input off wire fault: OW-B = an off-wire fault for connector B
Input off wire fault: OW-C = an off-wire fault for connector C
Input off wire fault: OW-D = an off-wire fault for connector D
Output no load or overload fault (OFLT): - When the bit is set
(1) an output fault has occurred. OFLT0 = output 0,
OFLT1 = output 1, OFLT2 corresponds to output 2,
OFLT3 = output 3.
Produces 2 00-05
06
07
RSVD = Reserved
Output Power Fault (OPWR): When the bit is set (1) Auxiliary
Power is not present.
RSVD = Reserved
Consumes 0 00-03
04-07
Output bits: When the bit is set (1), the output will be turned
on. Bit 00 corresponds to output O0, bit 01 corresponds to
output 01, bit 02 to output 02, bit 03 to output 03.
RSVD = Reserved