Rockwell Automation Publication 1788-UM058B-EN-P - September 2014 29
Set Up in the Studio 5000 Logix Designer Application Chapter 2
Configure the Linking Device
After the linking device is added to the I/O tree, you can configure the device
properties.
1. Right-click the linking device and choose Properties.
2. Click the Configuration tab to open the configuration page for the linking
device.
Process Catalog
Launches the HSProcessUtility that manages the GSD files and DTMs. If you
load new GSD files or DTMs, you launch the HSProcessUtility and update
(compile) the libraries.
IMPORTANT
You cannot configure a field device for cyclic communication unless the GSD file
is in the process utility catalog and the catalog has been updated (compiled).