Publication 1763-UM001D-EN-P - March 2011
96 Communication Connections
Power Options
Below are two options for powering the AIC+:
Use the 24V DC user power supply built into the MicroLogix™ 1000,
1200, or 1500 controller. The AIC+ is powered through a hard-wired
connection using a communication cable (1761-CBL-HM02, or
equivalent) connected to port 2.
Use an external DC power supply with the following specifications:
operating voltage: 24V DC (-15%/+20%)
output current: 150 mA minimum
rated NEC Class 2
Make a hard-wired connection from the external supply to the screw
terminals on the bottom of the AIC+.
ATTENTION
If you use an external power supply, it must be 24V DC
(-15%/+20%). Permanent damage results if miswired with
the wrong power source.
Zobrazit stránku 97