SSI Servo Module 17
Publication
1756-IN595A-EN-P - March 2004
Module Status Using the DRIVE Indicator
Figure 15 Drive Indicator LED
Flashing red
light
The axis servo loop error
tolerance has been
exceeded.
Correct the source of the
problem.
Clear the servo fault condition
using the Motion Axis Fault
Reset instruction.
Resume normal operation.
Steady red light An axis SSI feedback fault
has occurred.
Correct the source of the
problem by checking the SSI
device and power connections.
Clear the servo fault condition
using the Motion Axis Fault
Reset instruction.
Resume normal operation.
If the FDBK
LED displays:
The module status is: Take this action:
CH0 CH1
FDBK
DRIVE
OK
2 AXIS SERVO / SSI
FDBK
DRIVE
Drive
indicators