Publication 1753-PM001A-EN-P - November 2005
1-14 Connect to the GuardPLC Controller
Step 8: Change the Controller to STOP Mode
To change the controller to STOP mode, choose Resource>Stop from
the Control Panel or use the Stop icon.
When in STOP Mode, the Control Panel appears as follows:
Close the Control Panel.
Step 9: Reset the Controller to the Default Settings
In some cases, you may have to reset the GuardPLC controller to its
default IP address and SRS.
GuardPLC 1600 and 1800 controllers have a Reset button that is
accessible via a small hole directly to the right of the Ethernet ports on
top of the controller. The Reset button returns the IP address, SRS and
Password settings to:
Parameter Setting
IP Address 192.168.0.99
SRS 60000
Username Administrator
Password [none]