80 Rockwell Automation Publication 1732E-UM005A-EN-E - July 2012
Appendix C Module Tag Definitions
Access the Module Tags
When you access tags, you have two options. You can:
monitor tags – this option allows you to view tags and change their values
C.Ch0HEngineering
C.Ch1HEngineering
C.Ch2HEngineering
C.Ch3HEngineering
INT The high engineering value helps determine the engineering units the signal values scale into. The high
engineering term corresponds to the high signal value. The scaling equation used is as follows:
C.Ch0LClamp
C.Ch1LClamp
C.Ch2LClamp
C.Ch3LClamp
INT Sets the low clamp limit value for the channel.
See Clamping/Limiting on page 47 for more information.
C.Ch0HClamp
C.Ch1HClamp
C.Ch2HClamp
C.Ch3HClamp
INT Sets the high clamp limit value for the channel.
See Clamping/Limiting
on page 47 for more information.
C.Ch0Range
C.Ch1Range
C.Ch2Range
C.Ch3Range
SINT Configures the channel’s output range and determines the signal range the output channel can detect.
See Output Types and Ranges
on page 46 for more information.
C.Ch0FaultMode
C.Ch1FaultMode
C.Ch2FaultMode
C.Ch3FaultMode
SINT Selects the behavior the output channel should take if a communication fault occurs. Either hold last
state, go to a user-defined value, go to low clamp, or go to high clamp. Ch<0...3>FaultValue defines the
value to go to on fault if the bit is set.
C.Ch0ProgMode
C.Ch1ProgMode
C.Ch2ProgMode
C.Ch3ProgMode
SINT Selects the behavior the output channel should take if a communication fault occurs. Either hold last
state, go to a user-defined value, go to low clamp, or go to high clamp. Ch<0…3>FaultValue defines
the value to go to on fault if the bit is set.
C.Ch0LimitAlarmLatch
C.Ch1LimitAlarmLatch
C.Ch2LimitAlarmLatch
C.Ch3LimitAlarmLatch
SINT Enables latching for the clamp limit alarms. Latching causes the limit alarms to remain set until an
unlatch service is explicitly sent to the channel or alarm.
C.Ch0AlarmDisable
C.Ch1AlarmDisable
C.Ch2AlarmDisable
C.Ch3AlarmDisable
SINT Disables all alarms for the channel:
0 – Alarms are not disabled
1 – Alarms are disabled
Configuration Tags (1732E-OF4M12R)
Tag Name Data Type Definition
Data =
(Signal-LowSignal)(HighEngineering-LowEngineering)
High Signal - Low Signal
+ Low Engineering
Output Tags (1732E-OF4M12R)
Tag Name Data Type Definition
O.Ch0Data
O.Ch1Data
O.Ch2Data
O.Ch3Data
INT The channel output signal represented in counts where -32,768 counts is the minimum detectable
output signal and 32,767 counts is the maximum detectable.