20 Rockwell Automation Publication 1732E-UM005A-EN-E - July 2012
Chapter 3 Configure Your Analog Input and Output Modules with RSLogix 5000 Software
3. The New Module dialog appears.
Fill in the Module Properties information as shown, and then click OK.
Note that we have used the following properties in this example:
To add the 1732E-OF4M12R Analog output module, follow the same
steps. After adding the modules to your project, the I/O Configuration
tree should appear as follows:
This example uses default Module Definition and configuration
properties. To customize your module configuration, go to:
Edit Your 1732E-IF4M12R Configuration
on page 21
Edit Your 1732E-OF4M12R Configuration on page 30
Field Name Value
Name TEST_1732EIF4M12R
IP address 192.168.1.3
Electronic keying Compatible Module
Revision 1.1
Connection Input Only
(This parameter is Exclusive Owner for
1732E-OF4M12R)