Rockwell Automation Publication 1732E-UM005A-EN-E - July 2012 77
Appendix
C
Module Tag Definitions
The 1732E-IF4M12R and 1732E-OF4M12R modules have the following sets
of tags:
• Configuration
• Input
• Output (for 1732E-OF4M12R only)
Module Tags for 1732E-IF4M12R
Input Tags (1732E-IF4M12R)
Tag Name Data Type Definition
I.Fault DINT Collection of all module level fault bits.
I.Ch0Data
I.Ch1Data
I.Ch2Data
I.Ch3Data
INT The channel input signal represented in counts where -32,768 counts is the minimum detectable input signal and
32,767 counts is the maximum detectable.
I.Ch0Fault
I.Ch1Fault
I.Ch2Fault
I.Ch3Fault
BOOL Individual channel fault status bit. Indicates a ‘hard’ fault has occurred on the channel that means: calibration is
ongoing; or if an input, an overrange or underrange condition is present These bits also are set by the controller if
communication is lost with the I/O module.
I.Ch0Calibration
I.Ch1Calibration
I.Ch2Calibration
I.Ch3Calibration
BOOL Indicates if calibration is currently in progress on a channel.
I.Ch0Lalarm
I.Ch1Lalarm
I.Ch2Lalarm
I.Ch3Lalarm
BOOL Low alarm bits that set when the input signal moves beneath the configured low alarm trigger point,
C.Ch<0...3>LAlarmLimit. Remains set until the input signal moves above the trigger point, unless latched via
C.Ch<0...3>LimitAlarmLatch.
I.Ch0HAlarm
I.Ch1HAlarm
I.Ch2HAlarm
I.Ch3HAlarm
BOOL High alarm bit that sets when the input signal moves above the configured high alarm trigger point,
Ch<0…3>HAlarmLimit. emains set until the input signal moves below the trigger point, unless latched via
Ch<0…3>LimitAlarmLatch of the high alarm trigger point.
I.Ch0LLAlarm
I.Ch1LLAlarm
I.Ch2LLAlarm
I.Ch3LLAlarm
BOOL Low low alarm bit that sets when the input signal moves beneath the configured low low alarm trigger point,
Ch<0…3>LLAlarmLimit. Remains set until the input signal moves above the trigger point, unless latched via
Ch<0…3>LimitAlarmLatch.
I.Ch0HHAlarm
I.Ch0HHAlarm
I.Ch0HHAlarm
I.Ch0HHAlarm
BOOL High high alarm bit that sets when the input signal moves above the configured high high alarm trigger point,
Ch<0…3>LimitAlarmLatch.
I.Ch0Underrange
I.Ch1Underrange
I.Ch1Underrange
I.Ch1Underrange
BOOL Alarm bits indicating the channel’s input is less than the minimum detectable input signal.