Rockwell-automation 1560E SMC Flex Smart Motor Controller Uživatelský manuál Strana 16

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 198
  • Tabulka s obsahem
  • ŘEŠENÍ PROBLÉMŮ
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 15
1-6 Product Overview
%5-"%.0*UNE
Starting Modes (cont.) Preset Slow Speed
This option can be used in applications that require a slow-speed jog for
general purpose positioning. Preset Slow Speed provides either 7% of
base speed (low) or 15% of base speed (high) settings in the forward
direction. Reverse can also be programmed and offers 10% of base speed
(low) and 20% of base speed (high) settings.
Run
Forward
15% – High
7% – Low
10% – Low
20% – High
Reverse
Time (seconds)
Start
RunRun
Forward
15% – High
7% – Low
10% – Low
20% – High
Reverse
Time (seconds)
Start
Forward
15% – High
7% – Low
10% – Low
20% – High
Reverse
Time (seconds)
Start
Figure 1.6 – Preset Slow Speed Option
Important: Slow speed running is not intended for continuous operation due
to reduced motor cooling. The two starts per hour limitation also applies to
slow speed operation. This option employs a cycle-skipping scheme which
produces limited torque. Applications should be checked with the factory.