Trusted
TM
TMR Module T8160
Issue 13 May 13 PD-T8160 19
EXTRA INFORMATION
TMR Interface Status word format
Bit No. Description State
0
TMR Interface Slice A
See TMR Interface Slice status information.
1
TMR Interface Slice A
See TMR Interface Slice status information.
2
TMR Interface Slice B
See TMR Interface Slice status information.
3
TMR Interface Slice B
See TMR Interface Slice status information.
4
TMR Interface Slice C
See TMR Interface Slice status information.
5
TMR Interface Slice C
See TMR Interface Slice
status information.
6
Not Used
7
Not Used
8
Not Used
9
Not Used
10
Not Used
11
Active/Standby
0
Standby, 1
-
Active
12
Educated
0
uneducated, 1
-
educated.
13
Impending Module
0
ejectors open, 1
-
ejectors closed
14
Module online
0
TMR Interface offline, 1
-
TMR Interface online
15
Permissible Slot
0
Invalid Slot, 1
-
Permitted
TMR Interface Slice status information.
Bit n+1 Bit n State
0
0
Healthy slice
0
1
Transient fault
1
0
Hard fault
1
1
Unknown
Transceiver variable
Each of the 16 variables has the following configuration
Transceiver A bits 0,1
Transceiver B bits 2,3
Transceiver C bits 4,5
Bit n+1 Bit n State
0
0
Transceiver Healthy
0
1
Transceiver transient fault
1
0
Transceiver hard fault
1
1
Unknown
Notes:
1. All parameters must be supplied, even for virtual boards.
2. This module must appear before any attached Regent modules in the rack list.
3. The Permissible Slot status bit is 1 when the TMR Interface module has been correctly
configured in the I/O Connections and in the System Configuration Tool, even if the module is
not present.
4. If the Module On-line status bit is zero, the other status bits should not be used.