DC Digital Output Module
(T7441A)
12
Industrial Control Services
Minimum Load
0 mA
On State Drop
0.5 volts maximum @ 2 amps
Surge Current
15 amps, 20 msec
Output Leakage
1 mA maximum
Fusing
One 3 A, 250 V, fast
-
acting
(3AG) per output, located
inside module
Turn
-
On Delay
1.0 msec, maximum
Turn
-
Off Delay
1.0 msec,
maximum
Heat Dissipation
16 Watts, 54 BTUs/hour
Over voltage Protection
45 VDC, continuous
Isolation
2500 volts minimum (field
wiring to control logic)
2500 volts minimum (output
group 1
-
8 to output group 9
-
16)
Operating Temperature
0°
to 60
°
C
(32
°
to 140
°
F)
Storage Temperature
-
40
°
to 85
°
C
(-
40
°
to 185
°
F)
Op
erating Humidity
0 to 95% relative humidity,
non
-
condensing
Vibration
10 to 55 Hz:
±0.15mm
Shock
Operating:
15 g, ½ sine wave, 11 msec
Electromagnetic
Interference
IEC 801 Part 2
-
Electrostatic
Discharges
IEC 801 Part 3
-
Radiated
Electromagnetic Fields
Level 3: Contact discharge of
6 kV
Level 3: 10 V/M, 27 MHz
-
500 MHz