User ManualXM Dynamic Measurement ModuleCatalog Number 1440-DYN02-01RJ

Strany 2 - Important User Information

10 Publication ICM-UM002F-EN-E - March 2013Chapter 1 IntroductionModule ComponentsThe Dynamic Measurement module consists of a terminal base un

Strany 3 - Table of Contents

100 Publication ICM-UM002F-EN-E - March 2013Appendix A I/O Data TagsAlarm4SpeedRangeEn BOOL Decimal 0 = Disable (Default)1 = EnableAlarm5SpeedR

Strany 4

Publication ICM-UM002F-EN-E - March 2013 101I/O Data Tags Apendix AOutput Data TypeModule-defined Data Type: AB:1440_VDP:O:0Member Name Type De

Strany 5

102 Publication ICM-UM002F-EN-E - March 2013Appendix A I/O Data TagsNotes:

Strany 6

Publication ICM-UM002F-EN-E - March 2013 103Appendix BCIP ObjectsThis appendix defines the specific CIP Objects, Instances, Attributes, and Services s

Strany 7

104 Publication ICM-UM002F-EN-E - March 2013Appendix B CIP ObjectsIdentity Object(Class Code 01H)The Identity Object provides identification an

Strany 8 - Additional Resources

Publication ICM-UM002F-EN-E - March 2013 105CIP Objects Appendix BStatusThe Status is a 16 bit value. The following bits are implemented.Identi

Strany 9 - Introduction

106 Publication ICM-UM002F-EN-E - March 2013Appendix B CIP ObjectsServicesDeviceNet Object(Class Code 03H)The DeviceNet Object is used to provi

Strany 10 - Module Components

Publication ICM-UM002F-EN-E - March 2013 107CIP Objects Appendix BServicesAssembly Object(Class Code 04H)The Assembly Object binds attributes o

Strany 11 - ATTENTION

108 Publication ICM-UM002F-EN-E - March 2013Appendix B CIP ObjectsInstancesInstance AttributesTable B.1 Assembly Object InstancesInstance Name

Strany 12 - Chapter 1 Introduction

Publication ICM-UM002F-EN-E - March 2013 109CIP Objects Appendix BAssembly Instance Attribute Data FormatInstance 100 - Alarm and Relay StatusT

Strany 13

Publication ICM-UM002F-EN-E - March 2013 11Introduction Chapter 1XM BusThe XM Bus connector, located on each side of Dynamic Measurement module

Strany 14

110 Publication ICM-UM002F-EN-E - March 2013Appendix B CIP ObjectsInstance 199 - Dynamic AssemblyThis Assembly instance can be created and conf

Strany 15

Publication ICM-UM002F-EN-E - March 2013 111CIP Objects Appendix B21 1D 03 24 ii 30 0B Alarm 31Dh1 - 16 AlarmLDangerLimit 11 REAL21 1D 03 24 ii

Strany 16

112 Publication ICM-UM002F-EN-E - March 2013Appendix B CIP ObjectsThe dynamic Assembly instance must be instantiated with a call to the class l

Strany 17

Publication ICM-UM002F-EN-E - March 2013 113CIP Objects Appendix BInstancesInstance AttributesTable B.7 Connection Object InstancesInstance Des

Strany 18 - Requirements

114 Publication ICM-UM002F-EN-E - March 2013Appendix B CIP ObjectsServicesDiscrete Input Point Object(Class ID 08H)The Discrete Input Point Obj

Strany 19 - Grounding Requirements

Publication ICM-UM002F-EN-E - March 2013 115CIP Objects Appendix BInstance AttributesServices(1)The AlarmLimitMultiply output tag in the RSLogi

Strany 20 - DIN Rail Grounding

116 Publication ICM-UM002F-EN-E - March 2013Appendix B CIP ObjectsAnalog Input Point(Class ID 0AH)The Analog Input Point Object models simple a

Strany 21 - Panel/Wall Mount Grounding

Publication ICM-UM002F-EN-E - March 2013 117CIP Objects Appendix BServicesParameter Object(Class ID 0FH)The Parameter Object provides the inter

Strany 22 - 24V Common Grounding

118 Publication ICM-UM002F-EN-E - March 2013Appendix B CIP ObjectsClass AttributesInstancesThere are 39 instances of this object.Table B.17 Par

Strany 23 - Terminating Resistors

Publication ICM-UM002F-EN-E - March 2013 119CIP Objects Appendix B5 No Starting Order for Channel 0 Sum Harmonics meas.USINT 0=11=22=33=44=536

Strany 24 - Base Unit

12 Publication ICM-UM002F-EN-E - March 2013Chapter 1 IntroductionNotes:

Strany 25 - IMPORTANT

120 Publication ICM-UM002F-EN-E - March 2013Appendix B CIP Objects13 No Alarm 3 Measurement ID USINT (same as above) 114 No Alarm 4 Measurement

Strany 26 - Panel/Wall Mounting

Publication ICM-UM002F-EN-E - March 2013 121CIP Objects Appendix B(1)Alarms 6-15 are not available when the module is configured in the RSLogix

Strany 27 - Connecting Wiring for Your

122 Publication ICM-UM002F-EN-E - March 2013Appendix B CIP ObjectsServices(1)Attributes can only be set while the device is in Program Mode. Se

Strany 28 - Terminal Block Assignments

Publication ICM-UM002F-EN-E - March 2013 123CIP Objects Appendix BInstancesA module provides only a single instance (instance 1) of the Acknowl

Strany 29

124 Publication ICM-UM002F-EN-E - March 2013Appendix B CIP ObjectsInstancesThere are 16 instances of this object.Instance AttributesIMPORTANTAl

Strany 30 - Connecting the Power Supply

Publication ICM-UM002F-EN-E - March 2013 125CIP Objects Appendix B10 Get/Set AlarmLAlertLimit REAL The lesser threshold value for the Alert sta

Strany 31

126 Publication ICM-UM002F-EN-E - March 2013Appendix B CIP ObjectsServices(1)Attributes can only be set while the device is in Program Mode. Se

Strany 32 - Shielded Tacho Sensor

Publication ICM-UM002F-EN-E - March 2013 127CIP Objects Appendix BInstance AttributesServices(1)Attributes can only be set while the device is

Strany 33 - Tach Input Signal

128 Publication ICM-UM002F-EN-E - March 2013Appendix B CIP ObjectsChannel Object(Class ID 31FH)The Channel Object models front-end processing p

Strany 34 - Connecting the Transducer

Publication ICM-UM002F-EN-E - March 2013 129CIP Objects Appendix B5 Get/Set Low Cutoff FrequencyUSINT The effective high pass filter (low frequ

Strany 35 - Channel 0 Input Signal

13Publication ICM-UM002F-EN-E - March 2013 13Chapter 2Installing the XM Dynamic Measurement ModuleThis chapter discusses how to install and wire the D

Strany 36

130 Publication ICM-UM002F-EN-E - March 2013Appendix B CIP ObjectsServices(1)Attributes can only be set while the device is in Program Mode. Se

Strany 37

Publication ICM-UM002F-EN-E - March 2013 131CIP Objects Appendix BInstance AttributesSetting the Device Mode attribute to 1 (RUN) is equivalent

Strany 38 - Signal Common

132 Publication ICM-UM002F-EN-E - March 2013Appendix B CIP ObjectsOverall Measurement Object(Class ID 322H)The Overall Measurement Object model

Strany 39 - Connecting a Powered Sensor

Publication ICM-UM002F-EN-E - March 2013 133CIP Objects Appendix B4 Get Status BOOL Indicates if a fault or alarm has occurred.0 = Operating wi

Strany 40

134 Publication ICM-UM002F-EN-E - March 2013Appendix B CIP ObjectsServices(1)Attributes can only be set while the device is in Program Mode. Se

Strany 41

Publication ICM-UM002F-EN-E - March 2013 135CIP Objects Appendix BInstance AttributesTable B.36 Relay Object Instance AttributesAttr IDAccess R

Strany 42

136 Publication ICM-UM002F-EN-E - March 2013Appendix B CIP ObjectsServices(1)Attributes can only be set while the device is in Program Mode. Se

Strany 43

Publication ICM-UM002F-EN-E - March 2013 137CIP Objects Appendix BSpectrum Waveform Measurement Object(Class ID 324H)The Spectrum/Waveform Meas

Strany 44

138 Publication ICM-UM002F-EN-E - March 2013Appendix B CIP Objects6 Get/Set FMAX REAL The maximum frequency or order of the spectrum data.0...2

Strany 45

Publication ICM-UM002F-EN-E - March 2013 139CIP Objects Appendix BServices(1)Attributes can only be set while the device is in Program Mode. Se

Strany 46

14 Publication ICM-UM002F-EN-E - March 2013Chapter 2 Installing the XM Dynamic Measurement ModuleATTENTIONEnvironment and EnclosureThis equipme

Strany 47 - XM Bus Connection

140 Publication ICM-UM002F-EN-E - March 2013Appendix B CIP ObjectsGet_Spectrum_Chunk/Get_Waveform_ChunkThese services return a portion of the r

Strany 48

Publication ICM-UM002F-EN-E - March 2013 141CIP Objects Appendix BSpectrum Lines. To convert the normalized spectrum data into floating point v

Strany 49 - Mounting the Module

142 Publication ICM-UM002F-EN-E - March 2013Appendix B CIP ObjectsThe Waveform Data structure contains an array of values that, taken together,

Strany 50 - Basic Operations

Publication ICM-UM002F-EN-E - March 2013 143CIP Objects Appendix BTable B.42 Get_Spectrum_Chunk/Get_Waveform_Chunk Request ParametersName Data

Strany 51 - 1440-DYN02-01RJ

144 Publication ICM-UM002F-EN-E - March 2013Appendix B CIP ObjectsSpeed Measurement Object(Class ID 325H)The Speed Measurement Object models a

Strany 52

Publication ICM-UM002F-EN-E - March 2013 145CIP Objects Appendix BServices(1)Attributes can only be set while the device is in Program Mode. Se

Strany 53 - Configure the Module

146 Publication ICM-UM002F-EN-E - March 2013Appendix B CIP ObjectsServices(1)Attributes can only be set while the device is in Program Mode. Se

Strany 54

Publication ICM-UM002F-EN-E - March 2013 147CIP Objects Appendix BTransducer Object(Class ID 328H)The Transducer Object models a transducer.Cla

Strany 55 - Software

148 Publication ICM-UM002F-EN-E - March 2013Appendix B CIP Objects6 Get/Set Sensitivity Units ENGUNIT Units of the denominator of the Sensitivi

Strany 56 - I/O Configuration Tree

Publication ICM-UM002F-EN-E - March 2013 149CIP Objects Appendix BServices(1)Attributes can only be set while the device is in Program Mode. Se

Strany 57 - Profiles

Publication ICM-UM002F-EN-E - March 2013 15Installing the XM Dynamic Measurement Module Chapter 2European Hazardous Location ApprovalThe follow

Strany 58 - 6. Click OK

150 Publication ICM-UM002F-EN-E - March 2013Appendix B CIP ObjectsInstance AttributesServicesTable B.52 Vector Measurement Object Instance Attr

Strany 59 - Properties

Publication ICM-UM002F-EN-E - March 2013 151GlossaryaveragingThe process of combining multiple data samples to minimize the influence of transient sig

Strany 60

152 Publication ICM-UM002F-EN-E - March 2013GlossaryEarth/GroundA conducting path between an electric circuit or equipment and ground for safety or EM

Strany 61

Publication ICM-UM002F-EN-E - March 2013 153GlossaryNVS (Non-Volatile Storage)NVS is the permanent memory of an XM module. Modules store parameters an

Strany 62

154 Publication ICM-UM002F-EN-E - March 2013Glossarysignal detection Defines the method of conditioning or measuring a dynamic input signal. Peak (0 t

Strany 63

Publication ICM-UM002F-EN-E - March 2013 155IndexNumerics1440-ACNR 11, 23, 551440-DYN02-01RJdescription 10install on terminal base 491440-TBS-J 10desc

Strany 64

156 Publication ICM-UM002F-EN-E - March 2013Indexdownload program to controller 84Dynamic Measurement moduleCIP objects 103components 10configure 55gr

Strany 65

Publication ICM-UM002F-EN-E - March 2013 157Indextachometer channel object 145tachometer parameters 68Tachometer Status indicator 89tachometer, wiring

Strany 66

158 Publication ICM-UM002F-EN-E - March 2013IndexNotes:

Strany 68

16 Publication ICM-UM002F-EN-E - March 2013Chapter 2 Installing the XM Dynamic Measurement ModuleWARNINGSecure any external connections that ma

Strany 69

Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400Publication ICM-UM002F-EN-E - Marc

Strany 70

Publication ICM-UM002F-EN-E - March 2013 17Installing the XM Dynamic Measurement Module Chapter 2North American Hazardous Location ApprovalThe

Strany 71

18 Publication ICM-UM002F-EN-E - March 2013Chapter 2 Installing the XM Dynamic Measurement ModuleXM Installation RequirementsThis section descr

Strany 72

Publication ICM-UM002F-EN-E - March 2013 19Installing the XM Dynamic Measurement Module Chapter 2Figure 2.1 XM Modules with Separate Power Conn

Strany 73

Important User InformationSolid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines

Strany 74

20 Publication ICM-UM002F-EN-E - March 2013Chapter 2 Installing the XM Dynamic Measurement ModuleDIN Rail GroundingThe DIN Rail must be connect

Strany 75 - Configure the Band Properties

Publication ICM-UM002F-EN-E - March 2013 21Installing the XM Dynamic Measurement Module Chapter 2Panel/Wall Mount GroundingThe XM modules can a

Strany 76

22 Publication ICM-UM002F-EN-E - March 2013Chapter 2 Installing the XM Dynamic Measurement ModuleFigure 2.4 Panel/Wall Mount Grounding1 Use 14

Strany 77

Publication ICM-UM002F-EN-E - March 2013 23Installing the XM Dynamic Measurement Module Chapter 2Transducer GroundMake certain the transducers

Strany 78 - Clear to disable the alarm

24 Publication ICM-UM002F-EN-E - March 2013Chapter 2 Installing the XM Dynamic Measurement ModuleMounting the Terminal Base UnitThe XM family i

Strany 79

Publication ICM-UM002F-EN-E - March 2013 25Installing the XM Dynamic Measurement Module Chapter 22. Slide the terminal base unit over leaving r

Strany 80

26 Publication ICM-UM002F-EN-E - March 2013Chapter 2 Installing the XM Dynamic Measurement Module4. Press down on the terminal base unit to loc

Strany 81

Publication ICM-UM002F-EN-E - March 2013 27Installing the XM Dynamic Measurement Module Chapter 21. Lay out the required points on the wall/pan

Strany 82

28 Publication ICM-UM002F-EN-E - March 2013Chapter 2 Installing the XM Dynamic Measurement ModuleFigure 2.5 1440-TBS-J Terminal Base Unit Termi

Strany 83

Publication ICM-UM002F-EN-E - March 2013 29Installing the XM Dynamic Measurement Module Chapter 28 Not Connected9 Functional Earth Connection

Strany 84

3Publication ICM-UM002F-EN-E - March 2013 3Table of ContentsPrefaceWhat This Preface Contains . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Strany 85

30 Publication ICM-UM002F-EN-E - March 2013Chapter 2 Installing the XM Dynamic Measurement ModuleConnecting the Power SupplyThe power supply to

Strany 86

Publication ICM-UM002F-EN-E - March 2013 31Installing the XM Dynamic Measurement Module Chapter 2Figure 2.6 DC Input Power Supply Connections C

Strany 87 - Troubleshoot the Module

32 Publication ICM-UM002F-EN-E - March 2013Chapter 2 Installing the XM Dynamic Measurement ModuleConnecting a Magnetic Pickup TachometerFigure

Strany 88

Publication ICM-UM002F-EN-E - March 2013 33Installing the XM Dynamic Measurement Module Chapter 2Connecting a Hall Effect Tachometer Sensor Fig

Strany 89

34 Publication ICM-UM002F-EN-E - March 2013Chapter 2 Installing the XM Dynamic Measurement ModuleConnecting the Buffered OutputsThe Dynamic Mea

Strany 90

Publication ICM-UM002F-EN-E - March 2013 35Installing the XM Dynamic Measurement Module Chapter 2Figure 2.12 IEPE Accelerometer to Channel 0 Wi

Strany 91 - I/O Data Tags

36 Publication ICM-UM002F-EN-E - March 2013Chapter 2 Installing the XM Dynamic Measurement ModuleConnecting a Non-contact Sensor The following

Strany 92 - Module-defined Data Types

Publication ICM-UM002F-EN-E - March 2013 37Installing the XM Dynamic Measurement Module Chapter 2Figure 2.15 Non-contact Sensor to Channel 1 Wi

Strany 93

38 Publication ICM-UM002F-EN-E - March 2013Chapter 2 Installing the XM Dynamic Measurement ModuleFigure 2.16 Velocity Sensor to Channel 0 Wirin

Strany 94 - Ch0SumHarmonics

Publication ICM-UM002F-EN-E - March 2013 39Installing the XM Dynamic Measurement Module Chapter 2Connecting a Powered SensorThe following figur

Strany 95 - Ch1SumHarmonics

4 Publication ICM-UM002F-EN-E - March 2013Table of ContentsConfigure the Spectrum Properties. . . . . . . . . . . . . . . . . . . . . . . . . 71Config

Strany 96 - Configuration Data Type

40 Publication ICM-UM002F-EN-E - March 2013Chapter 2 Installing the XM Dynamic Measurement ModuleFigure 2.19 Powered Sensor to Channel 1 Wiring

Strany 97

Publication ICM-UM002F-EN-E - March 2013 41Installing the XM Dynamic Measurement Module Chapter 2Figure 2.20 DC Voltage Signal to Channel 0 Wir

Strany 98

42 Publication ICM-UM002F-EN-E - March 2013Chapter 2 Installing the XM Dynamic Measurement ModuleConnecting an IEPE Accelerometer and Non-Conta

Strany 99

Publication ICM-UM002F-EN-E - March 2013 43Installing the XM Dynamic Measurement Module Chapter 2Connecting Two Accelerometers and a Non-Contac

Strany 100

44 Publication ICM-UM002F-EN-E - March 2013Chapter 2 Installing the XM Dynamic Measurement ModuleFigure 2.23 Two IEPE Accelerometers and a Non-

Strany 101 - Output Data Type

Publication ICM-UM002F-EN-E - March 2013 45Installing the XM Dynamic Measurement Module Chapter 2Connecting a Velocity Sensor and Two Non-Conta

Strany 102

46 Publication ICM-UM002F-EN-E - March 2013Chapter 2 Installing the XM Dynamic Measurement ModuleFigure 2.24 Velocity Sensor and Two Non-contac

Strany 103 - CIP Objects

Publication ICM-UM002F-EN-E - March 2013 47Installing the XM Dynamic Measurement Module Chapter 2Figure 2.25 Three Non-contact Sensors WiringXM

Strany 104 - (Class Code 01

48 Publication ICM-UM002F-EN-E - March 2013Chapter 2 Installing the XM Dynamic Measurement ModuleConnect the DeviceNet cable to the terminal ba

Strany 105

Publication ICM-UM002F-EN-E - March 2013 49Installing the XM Dynamic Measurement Module Chapter 2Mounting the ModuleThe Dynamic Measurement mod

Strany 106 - (Class Code 03

Publication ICM-UM002F-EN-E - March 2013 5Table of ContentsClass Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Strany 107 - Assembly Object

50 Publication ICM-UM002F-EN-E - March 2013Chapter 2 Installing the XM Dynamic Measurement Module1. Make certain the keyswitch (D) on the termi

Strany 108 - Instance Attributes

Publication ICM-UM002F-EN-E - March 2013 51Installing the XM Dynamic Measurement Module Chapter 2The module is shipped from the factory with th

Strany 109 - Request from a Master

52 Publication ICM-UM002F-EN-E - March 2013Chapter 2 Installing the XM Dynamic Measurement Module(1)Do not set the node address to 0. Node addr

Strany 110 - Appendix B CIP Objects

Publication ICM-UM002F-EN-E - March 2013 53Installing the XM Dynamic Measurement Module Chapter 2Power Up the ModuleThe module performs a self-

Strany 111 - CIP Objects Appendix B

54 Publication ICM-UM002F-EN-E - March 2013Chapter 2 Installing the XM Dynamic Measurement ModuleNotes:

Strany 112 - (Class ID 05H)

55Publication ICM-UM002F-EN-E - March 2013 55Chapter 3Configure XM Module in RSLogix 5000 SoftwareThe RSLogix 5000 software Add-on Profile (AOP) lets

Strany 113

56 Publication ICM-UM002F-EN-E - March 2013Chapter 3 Configure XM Module in RSLogix 5000 SoftwareFor more information about the 1440-ACNR, refe

Strany 114 - (Class ID 08H)

Publication ICM-UM002F-EN-E - March 2013 57Configure XM Module in RSLogix 5000 Software Chapter 33. Click the plus sign next to the Specialty f

Strany 115 - Services

58 Publication ICM-UM002F-EN-E - March 2013Chapter 3 Configure XM Module in RSLogix 5000 SoftwareThe New Module dialog box opens.5. From the Mo

Strany 116 - (Class ID 0A

Publication ICM-UM002F-EN-E - March 2013 59Configure XM Module in RSLogix 5000 Software Chapter 3Configure Module Properties Follow these steps

Strany 117 - (Class ID 0F

6 Publication ICM-UM002F-EN-E - March 2013Table of ContentsOverall Measurement Object(Class ID 322H) . . . . . . . . . . . . . . . . . . . . . . . .

Strany 118 - Class Attributes

60 Publication ICM-UM002F-EN-E - March 2013Chapter 3 Configure XM Module in RSLogix 5000 SoftwareConfigure the Module Definition PropertiesThe

Strany 119

Publication ICM-UM002F-EN-E - March 2013 61Configure XM Module in RSLogix 5000 Software Chapter 33. Click Channel Data tab to select the measur

Strany 120

62 Publication ICM-UM002F-EN-E - March 2013Chapter 3 Configure XM Module in RSLogix 5000 Software5. When finished selecting the measurements, c

Strany 121

Publication ICM-UM002F-EN-E - March 2013 63Configure XM Module in RSLogix 5000 Software Chapter 3Configure the Connection PropertiesUse the Con

Strany 122 - (Class ID 2BH)

64 Publication ICM-UM002F-EN-E - March 2013Chapter 3 Configure XM Module in RSLogix 5000 Software3. When finished, click one of these as needed

Strany 123 - (Class ID 31DH)

Publication ICM-UM002F-EN-E - March 2013 65Configure XM Module in RSLogix 5000 Software Chapter 31. From the Module Properties dialog box, clic

Strany 124

66 Publication ICM-UM002F-EN-E - March 2013Chapter 3 Configure XM Module in RSLogix 5000 SoftwareNominal Sensitivity Choose the sensitivity of

Strany 125

Publication ICM-UM002F-EN-E - March 2013 67Configure XM Module in RSLogix 5000 Software Chapter 3Full Scale Choose the maximum signal level ex

Strany 126 - (Class ID 31E

68 Publication ICM-UM002F-EN-E - March 2013Chapter 3 Configure XM Module in RSLogix 5000 Software4. When finished, click one of these as needed

Strany 127

Publication ICM-UM002F-EN-E - March 2013 69Configure XM Module in RSLogix 5000 Software Chapter 32. Configure the parameters, as necessary. In

Strany 128 - (Class ID 31F

7Publication ICM-UM001F-EN-E - March 2013 7PrefaceWhat This Preface ContainsThis preface describes how to use this manual.Who Should Use This ManualTh

Strany 129

70 Publication ICM-UM002F-EN-E - March 2013Chapter 3 Configure XM Module in RSLogix 5000 Software3. When finished, click one of these as needed

Strany 130 - (Class ID 320

Publication ICM-UM002F-EN-E - March 2013 71Configure XM Module in RSLogix 5000 Software Chapter 3Configure the Spectrum PropertiesThe Spectrum

Strany 131

72 Publication ICM-UM002F-EN-E - March 2013Chapter 3 Configure XM Module in RSLogix 5000 SoftwareSampling Mode continued.Frequency Maximum The

Strany 132 - (Class ID 322

Publication ICM-UM002F-EN-E - March 2013 73Configure XM Module in RSLogix 5000 Software Chapter 3Number of Spectrum Lines Choose the number of

Strany 133

74 Publication ICM-UM002F-EN-E - March 2013Chapter 3 Configure XM Module in RSLogix 5000 SoftwareFFT Window Type Choose the type of window to b

Strany 134 - (Class ID 323

Publication ICM-UM002F-EN-E - March 2013 75Configure XM Module in RSLogix 5000 Software Chapter 34. When finished, click one of these as needed

Strany 135

76 Publication ICM-UM002F-EN-E - March 2013Chapter 3 Configure XM Module in RSLogix 5000 Software1. From the Module Properties dialog box, clic

Strany 136

Publication ICM-UM002F-EN-E - March 2013 77Configure XM Module in RSLogix 5000 Software Chapter 34. When finished, click one of these as needed

Strany 137 - (Class ID 324

78 Publication ICM-UM002F-EN-E - March 2013Chapter 3 Configure XM Module in RSLogix 5000 SoftwareConfigure the Alarm PropertiesUse the Alarm ta

Strany 138

Publication ICM-UM002F-EN-E - March 2013 79Configure XM Module in RSLogix 5000 Software Chapter 3Measurement ID Choose the measurement and chan

Strany 139

8 Publication ICM-UM001F-EN-E - March 2013Preface Additional ResourcesThese documents contain additional information concerning related product

Strany 140

80 Publication ICM-UM002F-EN-E - March 2013Chapter 3 Configure XM Module in RSLogix 5000 SoftwareDeadband Enter the amount that the measured va

Strany 141

Publication ICM-UM002F-EN-E - March 2013 81Configure XM Module in RSLogix 5000 Software Chapter 34. When finished, click one of these as needed

Strany 142

82 Publication ICM-UM002F-EN-E - March 2013Chapter 3 Configure XM Module in RSLogix 5000 Software2. Configure the parameters, as necessary.In t

Strany 143

Publication ICM-UM002F-EN-E - March 2013 83Configure XM Module in RSLogix 5000 Software Chapter 33. When finished, click one of these as needed

Strany 144 - (Class ID 325

84 Publication ICM-UM002F-EN-E - March 2013Chapter 3 Configure XM Module in RSLogix 5000 SoftwareSave Module Configuration and Download to the

Strany 145 - (Class ID 326

Publication ICM-UM002F-EN-E - March 2013 85Configure XM Module in RSLogix 5000 Software Chapter 3• For RSLogix 5000 programming instructions, r

Strany 146

86 Publication ICM-UM002F-EN-E - March 2013Chapter 3 Configure XM Module in RSLogix 5000 SoftwareNotes:

Strany 147 - (Class ID 328

87Publication ICM-UM002F-EN-E - March 2013 87Chapter 4Troubleshoot the ModuleThis chapter provides information for diagnosing and troubleshooting your

Strany 148

88 Publication ICM-UM002F-EN-E - March 2013Chapter 4 Troubleshoot the ModuleModule Status (MS) IndicatorThe following table describes the modul

Strany 149 - (Class ID 329

Publication ICM-UM002F-EN-E - March 2013 89Troubleshoot the Module Chapter 4Tachometer Status IndicatorsThe following table describes the tacho

Strany 150

9Publication ICM-UM002F-EN-E - March 2013 9Chapter 1IntroductionThis chapter provides an overview of the Dynamic Measurement module. It also discusses

Strany 151 - Glossary

90 Publication ICM-UM002F-EN-E - March 2013Chapter 4 Troubleshoot the ModuleNotes:

Strany 152

91Publication ICM-UM002F-EN-E - March 2013 91Appendix AI/O Data TagsThis appendix describes the module-defined data types for the 1440-DYN02-01RJ stan

Strany 153

92 Publication ICM-UM002F-EN-E - March 2013Appendix A I/O Data TagsModule-defined Data TypesThe following tables list and describe module-defin

Strany 154

Publication ICM-UM002F-EN-E - March 2013 93I/O Data Tags Apendix AModulePowerFault BOOL Faults:25 0 = No fault on 24V supply1 = Fault on 24V su

Strany 155 - Numerics

94 Publication ICM-UM002F-EN-E - March 2013Appendix A I/O Data TagsAlarm0Alert BOOL Alarms:0 0 = Alarm 0 is not in Alert1 = Alarm 0 is in Alert

Strany 156

Publication ICM-UM002F-EN-E - March 2013 95I/O Data Tags Apendix A(1)The input data type name varies depending on the measurements you select i

Strany 157

96 Publication ICM-UM002F-EN-E - March 2013Appendix A I/O Data TagsConfiguration Data TypeModule-defined Data Type: AB:1440_VDP_ChConfig_Struct

Strany 158

Publication ICM-UM002F-EN-E - March 2013 97I/O Data Tags Apendix AHighPassFilterSelection SINT Decimal 0 = 0.2 Hz1 = 1 Hz2 = 5 Hz3 = 10 Hz (Def

Strany 159

98 Publication ICM-UM002F-EN-E - March 2013Appendix A I/O Data TagsModule-defined Data Type: AB:1440_VDP_AlarmConfig_Struct:C:0Member Name Type

Strany 160 - Documentation Feedback

Publication ICM-UM002F-EN-E - March 2013 99I/O Data Tags Apendix AModule-defined Data Type: AB:1440_VDP:C:0Member Name Type Default Display Sty