Mounting the Drive
3-11
3.2 Mounting the Drive
Refer to figures 3.4, 3.5, 3.6, and 3.7 for drive mounting
dimensions.
Attach the drive to the vertical surface using the mounting holes
provided. Frame size 2 and 3 drives should be mounted using 3/16”
(M5) bolts. Frame size 4 and 5 drives should be mounted using 1/4”
(M6) bolts. Frame size 6 drives should be mounted using 5/16” (M8)
bolts.
3.2.1 Verifying the Drive’s Watts Loss Rating
When mounting the drive inside another enclosure, determine the
watts loss rating of the drive from tables 2.1 and 2.2. This table lists
the typical full load power loss watts value at a carrier frequency of
4 kHz. (The 248 amp drive is rated at a carrier frequency value of 2
kHz.) Ensure that the enclosure is adequately ventilated with 0
° to
40
° C (32° to 104° F) ambient air.