Parameter Descriptions
11-15
Flux-up current is the amount of DC current equal to current limit, so
full flux can be established in the motor before acceleration.
Manual (0): Flux is established for Flux Up Time (58) before
acceleration
Auto (1): Flux is established for a calculated time period based on
motor nameplate data. Flux Up Time (58) is not used.
Sets the amount of time the drive will use to try to achieve full motor
stator flux. When a start command is issued, DC current at current
limit level is used to build stator flux before accelerating.
Sets the amount of filtering used to boost voltage during Sensorless
Vector operation.
57 Flux Up Mode
Range: 0 = Manual
1 = Automatic
Default: 0 = Manual
Access: 2 Path: Motor Control>Torq Attributes
See also: 53, 58
58 Flux Up Time
Range: 0.00 to 5.00 Sec [0.01 Sec]
Default: 0.0 Sec
Access: 2 Path: Motor Control>Torq Attributes
See also: 53, 58
59 SV Boost Filter
Range: 0 to 32767
Default: 500
Access: 2 Path: Motor Control>Torq Attributes
See also: