Configuring the UDC Module’s Registers
3-45
Parallel Power Module C Status Register (Continued) 221/1221
GDI Fault C Bit 7
The GDI Fault C bit is set if a fault is
detected in the power supply of Power
Module C’s Gate Driver Interface module.
Hex Value: 0080H
Sug. Var. Name: GDIC@
Access: Read only
UDC Error Code: N/A
LED: N/A
Charge Fault C Bit 8
The Charge Fault C bit is set if a charge bus
time-out fault occurs in Power Module C
(refer also to register 202/1202, bit 6).
Hex Value: 0100H
Sug. Var. Name: CHGC@
Access: Read only
UDC Error Code: N/A
LED: N/A
Over Temperature C Bit 12
The Over Temperature C bit is set if an over
temperature fault or warning occurs in
Power Module C.
Hex Value: 1000H
Sug. Var. Name: OTC@
Access: Read only
UDC Error Code: N/A
LED: N/A
Phase U Current Sharing C Bit 13
The Phase U Current Sharing C bit is set if a
Power Module C is not carrying its share of
the phase U current.
Hex Value: 2000H
Sug. Var. Name: U_SHRC@
Access: Read only
UDC Error Code: N/A
LED: N/A
Phase V Current Sharing C Bit 14
The Phase V Current Sharing C bit is set if
Power Module C is not carrying its share of
the phase V current.
Hex Value: 4000H
Sug. Var. Name: V_SHRC@
Access: Read only
UDC Error Code: N/A
LED: N/A
Phase W Current Sharing C Bit 15
The Phase W Current Sharing C bit is set if
Power Module C is not carrying its share of
the phase W current.
Hex Value: 8000H
Sug. Var. Name: W_SHRC@
Access: Read only
UDC Error Code: N/A
LED: N/A