Configuring the UDC Module’s Registers
3-47
Meter Port 1
Port 1 UDC Register Number 1002
Enter the UDC register number (0 - 2044) to be mapped to meter
port 1.
Sug. Var. Name:
N/A
Units:
N/A
Range:
N/A
Access:
Read/Write
Port 1 Bit Number Register 1003
Bit number of the UDC register specified in register 1002 that is to be
mapped to port 1. Enter a value of 100 (bit 00) to 115 (bit 15) as
required. Enter a value of zero if all of the register’s bits are to be
displayed.
Sug. Var. Name:
N/A
Units:
N/A
Range:
N/A
Access:
Read/Write
Port 1 Maximum Value Register 1004
Set this register to the number that will represent +10V. The
maximum allowable value is 32767.
Sug. Var. Name:
N/A
Units:
N/A
Range:
N/A
Access:
Read/Write
Port 1 Minimum Value Register 1005
Set this register equal to the number that will represent -10V. The
minimum allowable value is -32768.
Sug. Var. Name:
N/A
Units:
N/A
Range:
N/A
Access:
Read/Write