C-30
DeviceNet Adapter for use with DPI AC Drives
Instance Attributes
6 Get Number of
Recorded Faults
WORD Number of faults/events in the
queue. A “0” indicates the fault
queue is empty.
7 Get Fault Parameter
Reference
WORD Reserved
Attribute
ID
Access
Rule Name Data Type Description
Attribute
ID
Access
Rule Name Data Type Description
0 Get Full/All
Information
STRUCT of
WORD
STRUCT of
BYTE
BYTE
STRING[16]
STRUCT of
LWORD
BOOL[16]
WORD
CONTAINER[n]
Fault code
Fault source
DPI port
DPI Device Object
Fault text
Fault time stamp
Timer value (0 = Timer not
supported)
BOOL[0]: (0 = invalid data,
1 = valid data)
BOOL[1]: (0 = elapsed time,
1 = real time)
BOOL[2 - 15]: Not used
Reserved
Reserved
1GetBasic
Information
STRUCT of
WORD
STRUCT of
BYTE
BYTE
STRUCT of
LWORD
BOOL[16]
Fault code
Fault source
DPI port
DPI Device Object
Fault time stamp
Timer value (0 = Timer not
supported)
BOOL[0]: (0 = invalid data,
1 = valid data)
BOOL[1]: (0 = elapsed time,
1 = real time)
BOOL[2 - 15]: Not used