Triguard
SPECIFICATION
Model
MHB44IND
Channels
4 x pulse
inputs
4 x analogue
outputs
Architecture
TMR
Indicators
Health,
3 x On
Line
Test
Point
4 x signal,
1 x common
Output
range
0 to
22mA
Maximum
resistive
field
load
400ohm
Resolution
6.25
µ
A steps
Accuracy
@
@ 25°C
+
0.2%
of
full
signal
range
Maximum
input
ripple
voltage
@24V
field
supply
12V
peak
to
peak
Maximum
input
ripple
frequency
120Hz
Stability
(temperature
coefficient)
15ppm/°C
Isolation
1kV
to
system,
commoned
supply
Field
pow
er
supply:
Voltage
range
+18Vdc
to
30Vdc
Module
power
consumption
5.5W
Pulse
input
waveform
Sine/Square/Pulse
Pulse
input
amplitude
100mV
to
132V
peak
(
NOTE
:
For
sinewave
inputs
less
than
10Hz
amplitude
minimum
rises
linearly
to
200mV
at
1Hz)
Pulse
input
duty
cycle
10
to
90%
up
to
3.5kHz
Pulse
input
width
(minimum)
14ms
above
3.5kHz
Pulse
input
impedance
10k
ohm
Pulse
input
frequency
resolution
16
bits
Pulse
input
frequency
accuracy
± 0.01%
1Hz
to
35kHz
Overall
size
(mm)
Overall
size
(inches)
400
(9U)H
x 397L
x 28W
15.75H
x 15.63L
x 1.1W
Weight
1.7kg
Komentáře k této Příručce