FACTORYTALK VIEW SITE EDITION USERS GUIDE
14–16
• • • • •
3. In the Redundancy tab, select the check box, Provide redundancy using a
secondary server.
4. Specify the name of the secondary HMI servers host computer, and the switchover
option for this redundant server pair.
For details about options in the Redundancy tab, click Help.
Replicate changes to the secondary HMI server
While the primary HMI server is active, you can modify HMI project components, such
as graphic displays, configuration files, and log files. However, any changes you make on
the primary server are not synchronized automatically on the secondary server.
To synchronize server settings and contents, you must replicate changes manually, from
the primary to the secondary server. The replicate operation copies the primary servers
configuration files, including settings in the Components tab, to the secondary server.
For example, if an On Active and a Shutdown macro are selected for the primary server,
the settings will be replicated to the secondary. This means that the same macros specified
for the primary server will run when the secondary server becomes active or shuts down.