Rockwell-automation FactoryTalk View Site Edition Users Guide Uživatelský manuál Strana 263

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 696
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 262
12 SETTING UP FACTORYTALK ALARMS
12–7
• • • • •
12 • Placeholder
For information about setting up alarm servers in a FactoryTalk View SE application, see:
“Working with Rockwell Automation Device Servers” on page 12-18.
“Working with Tag Alarm and Event Servers” on page 12-21.
Level alarms
A level alarm compares an analog value against predefined limits (also called thresholds)
and triggers an alarm when a limit is exceeded. For information about setting up tag-based
level alarms, see page 12-24.
Level alarm limits
When defining a level alarm, you can assign any of the following limits, with different
levels of severity:
High High
High
Low
Low Low
The High and High High alarm conditions monitor for a rising value, and the Low and
Low Low conditions monitor for a decreasing value.
Example: Alarm limits
Zobrazit stránku 262
1 2 ... 258 259 260 261 262 263 264 265 266 267 268 ... 695 696

Komentáře k této Příručce

Žádné komentáře