Rockwell-automation FactoryTalk View Site Edition Installation Guide Uživatelský manuál Strana 42

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 173
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 41
FACTORYTALK VIEW INSTALLATION GUIDE
28
• • • • •
4. In the System Properties dialog box, click the
Advanced
tab.
5. In the Advanced tab, under Performance, click
Settings
.
6. In the Performance Options dialog box, click the
Data Execution Prevention
tab.
7. Select the option,
Turn on DEP for essential Windows programs and services
only
, and then click OK.
For Windows XP or Windows Server 2003
1. Open the Windows Control Panel, and then double-click
System
.
2. In the Advanced tab, under Performance, click
Settings
.
3. In the Performance Options dialog box, click the
Data Execution Prevention
tab.
4. Select the option,
Turn on DEP for essential Windows programs and services
only
, and then click
Apply
.
Remove unnecessary DCOM networking protocols
If multiple DCOM protocols are installed and configured on the computer, performance of
communications in a FactoryTalk View SE system can be adversely impacted. To ensure
that DCOM communications function correctly, and do not affect the performance of the
system, remove all protocols other than TCP/IP.
To remove unnecessary DCOM protocols
1. Select
Start >
Run.
2. In the Run dialog box, type
dcomcnfg
, and then click
OK
.
3. In the Component Services tool, expand Component Services, open the Computers
folder, right-click
My Computer
, and then select
Properties
.
4. Click the Default Protocols tab. If the DCOM Protocols list shows protocols in
addition to TCP/IP, remove those unnecessary protocols. For example, remove the
protocol Connection-oriented SPX.
FTViewSEInstallENU.book Page 28 Wednesday, July 16, 2014 10:53 AM
Zobrazit stránku 41
1 2 ... 37 38 39 40 41 42 43 44 45 46 47 ... 172 173

Komentáře k této Příručce

Žádné komentáře