Trusted
TM
CS300 Bridge Module
Issue 02 Feb 10 PD-8162 12
The four backplane jumpers 0,1,2,3 (A,B,C) represent the binary address bits 1,2,4 & 8 respectively. A
f
itted jumper signals a binary digit1. The address is set to between 2 and 8. On the first CS300
chassis (containing the CS300 Bridge Modules), fit jumper 1 (A,B,C) to represent Trusted
TM
address
'2'. The jumpers on all three sets must be set to the same address. Leave the jumpers as they were on
the other CS300 chassis. It is usual to attach the chassis with address 2 to the first Expander Interface
Adapter socket, for both Trusted
TM
chassis and CS300 chassis. This makes the software configuration
easier.