Chapter 4 No-load Test
There are no specific T parameters to modify when commissioning a drive. Verify
the values and only modify per customer specifications.
P416 Flying Start Mode
0: Disable
1: Set Frequency
2: Stop Frequency Plus 5 Hz
3: Rated Frequency
0ON03Setup
P417 Flying Start Motor Speed Search Timeout (s) 50 ON 0 1000 R&D
P438 Flying Start Current Compensation Threshold 100 ON 0 199.99 R&D
P451 Low Speed Voltage Compensation (%) 0.99 OFF 0 10 Setup
P452 Low Speed Voltage Compensation Frequency
Threshold
20 ON 0 100 R&D
P455 Modulation Index 87.99 ON 0 199.99 Setup Improve the real output of inverter voltage value. For example:
rated voltage of the inverter for 10 kV, if the actual output is
9700V, the need to improve the actual output voltage to 10 kV,
need to change this value
P456 Motor Voltage Upper Limit 87.99 ON 0 199.99 R&D
P457 Flying Start Voltage Recovery Time (s)
(Low Speed Region)
5 ON 0 163.84 R&D
P459 Flying Start Voltage Recovery Time (s)
(High Speed Region)
5 ON 0 163.84 R&D
P460 Rated Output Frequency 50 OFF 0 75 R&D
(1) ON: Can be modified at any time. OFF: Drive must be off to modify.
(2) With Remote DCS only.
Table 12 - Setup and R&D Parameters (Continued)
P
Parameter
Description Default Modify
Root
(1)
Min.
Value
Max.
Value
Login
Level
Instruction
T
Parameter
Description Default Modify
Root
(1)
Min.
Value
Max.
Value
Login
Level
Instruction
T01 Fault-To-Bypass
0: Disable
1: Enable
0ON01 Setup
T02 Fault-To-Bypass Delay 3 ON 0 60 Setup While T1=1 valid
T03 Fault-To-Bypass Delay When Starting
the Motor (0...60s)
60 ON 0 60 Setup While T1=1 valid
T04 Fault-To-Bypass Minimum Frequency
0...Rated Frequency (Hz)
5ON0Rated
Frequency
Setup While T1=1 valid
T05 Auto Restart After Input Supply Power Loss
0: Disable
1: Enable
0ON01 Setup
T06 Input Supply Power Loss Time for
Auto Restart (0...20s)
20 ON 0 20 Setup
T07 Local Frequency Command Selection
0: Digital
1: Analog
0 ON 0 1 Setup If T7=0, enter the frequency on the HMI. If T7=1, use a
potentiometer to set the frequency on the LV Control
Cabinet. Confirm P262=1.