PowerFlex® 6000 Medium Voltage Variable Frequency Drive Commissioning ManualPublication 6000-IN007A-EN-PCommissioning Manual
10 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014PrefaceNotes:
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 11Chapter 1IntroductionOverviewInformation contained in this chapter will assist in co
12 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 1 IntroductionProcess FlowchartsDocumentation and Application ReviewReview a
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 13Introduction Chapter 1• PLC Program: The PLC I/O processes control signals within th
14 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 1 IntroductionOn-site Verification of Electrical System One-line DiagramOnce
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 15Chapter 2Preparation and InspectionGather Required Tools and Test EquipmentHand Tool
16 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 2 Preparation and InspectionLockout and tagout the input circuit breaker bef
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 17Preparation and Inspection Chapter 2Functional AssessmentAfter the components are vi
18 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 2 Preparation and InspectionTable 3 - Inspect Drive Components ChecklistBypa
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 19Preparation and Inspection Chapter 2Table 4 - Functional Assessment ChecklistBypass
Important User InformationRead this document and the documents listed in the additional resources section about installation, configuration, and opera
20 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 2 Preparation and InspectionInterconnection ReviewThe interconnection checkl
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 21Preparation and Inspection Chapter 2Installation ReviewPrior to commencing the commi
22 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 2 Preparation and InspectionElectrical Installation InspectionPower CablingT
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 23Preparation and Inspection Chapter 2Incoming Line and Outgoing Motor cables must be
24 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 2 Preparation and Inspection2. Disconnect four 380V AC cables (a, b, c, and
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 25Preparation and Inspection Chapter 25. Switch the miniature circuit breakers in the
26 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 2 Preparation and Inspection8. Disconnect the control cable of HECS.Figure 7
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 27Preparation and Inspection Chapter 210. Remove the Analog Interface board and discon
28 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 2 Preparation and Inspection5. Disconnect the Insulation Meter and jumpers i
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 29Preparation and Inspection Chapter 2Final Steps before Equipment is Ready for Energi
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 3Table of ContentsPrefaceIntroduction. . . . . . . . . . . . . . . . . . . . . . . . .
30 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 2 Preparation and InspectionNotes:
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 31Chapter 3CommissioningIntroductionA number of activities are required before the Con
32 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 CommissioningControl System Check SetupSimulate Closed Input Circuit Break
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 33Commissioning Chapter 3Figure 14 - LV Control CabinetFigure 15 - LV Panel in the Iso
34 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 CommissioningFigure 16 - AC/DC Power SuppliesTable 8 - Energize Control Ci
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 35Commissioning Chapter 3Control System CheckVerify Factory Default SettingsConfirm La
36 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning3. Press and confirm the Bypass Configuration matches one o
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 37Commissioning Chapter 3The Select Local Control? dialog box appears.5. Select to c
38 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 CommissioningThe Setup Login dialog box appears. Press .3. Enter the User
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 39Commissioning Chapter 3For the simulation tests, you only need to change two paramet
4 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Table of ContentsVerify E-Stop Functionality . . . . . . . . . . . . . . . . . . . .
40 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning3. Press “0” on the keypad dialog and press .Parameter 007 w
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 41Commissioning Chapter 3Verify Operation of Frequency StepsThere are two parts to thi
42 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning3. Press , and press in the Start Drive? dialog box to con
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 43Commissioning Chapter 35. Press and press in the Decel Speed by Step? dialog box
44 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning2. Press to accept and begin the simulation.Actual Frequenc
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 45Commissioning Chapter 3Simulate Warnings and FaultsThis section describes how to sim
46 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning3. Press to view alarm record..4. Remove the jumper wires t
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 47Commissioning Chapter 36. Press , and press to confirm the operation in the Reset
48 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning3. Press to confirm the Transformer Cabinet Main Cooling Fa
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 49Commissioning Chapter 33. Press and confirm the Power Module Cabinet Fan Fault.4.
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 5Table of ContentsSpeed Reference Functions. . . . . . . . . . . . . . . . . . . . . .
50 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning5. Press to return to the Main Interface Screen. 6. Press
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 51Commissioning Chapter 36. Press to remove the fault. Press to confirm operation
52 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning6. Under Control Owner Selection, press .7. Select to conf
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 53Commissioning Chapter 32. Open the Bypass cabinet door, and close QS2 and QS3.Verify
54 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 CommissioningBypass Isolation Switches1. Press from the Main Interface s
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 55Commissioning Chapter 33. Close the customer-supplied input circuit breaker by insta
56 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning2. Close the customer-supplied input circuit breaker by insta
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 57Commissioning Chapter 3Verify the input and output drive contactors are closed.4. Pr
58 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning5. Verify the input and output drive contactors are closed.By
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 59Commissioning Chapter 32. Press under Contactor Operation, and press to confirm..
6 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Table of ContentsNotes:
60 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning3. Press under Contactor Operation, and press to confirm..
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 61Commissioning Chapter 3Verify Operation of DCS Input and Output SignalsFigure 17 - S
62 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 CommissioningWhen the two terminals specified are shorted, verify the resu
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 63Commissioning Chapter 3Press to enter password details. Press when finished.3. P
64 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 CommissioningSet Date and Time ZoneTo access the Date and Time Zone settin
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 65Commissioning Chapter 3Change Time/Date/Regional Settings1. In Windows ME, press Ter
66 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 CommissioningNotes:
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 67Chapter 4No-load TestIntroductionNo-load TestThe No-load Test consists of the follow
68 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 4 No-load TestEnergize Drive Control CircuitThe “Energize Control Circuit” p
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 69No-load Test Chapter 4P091 Skip Frequency 1 Upper Limit 0 ON 0 75 R&DP092 Skip F
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 7PrefaceIntroductionThis document provides procedural information for commissioning Po
70 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 4 No-load TestThere are no specific T parameters to modify when commissionin
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 71No-load Test Chapter 4Parameters T11...T13To change Parameter T11:1. Press the T11 P
72 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 4 No-load Test2. In the Switch Method Selection dialog, press or . 3. If
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 73No-load Test Chapter 4Change Parameter T12:1. Press the T12 Parameter input field.2.
74 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 4 No-load TestChange Parameter T13:1. Press the T13 Parameter input field.2.
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 75No-load Test Chapter 4Close Isolation Switches in Bypass Cabinet1. Manual bypass (se
76 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 4 No-load TestOperate Motor by HMI1. From the Main Interface Screen, press t
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 77No-load Test Chapter 43. Press , and press in the Start Drive? dialog box to conf
78 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 4 No-load Test5. From the Main Interface Screen, press the Set Frequency: in
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 79No-load Test Chapter 47. Press , and press in the Start Drive? dialog box to conf
8 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014PrefaceIf the drawings require changes to suit the installation and application of th
80 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 4 No-load Test13. Switch on the customer-supplied control power, and push th
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 81Appendix ATorque RequirementsTorque RequirementsProper tightening torque must be use
82 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Appendix A Torque RequirementsNotes:
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 83Appendix BSingle Line DiagramsFigure 18 - PowerFlex 6000 without BypassQFInput Circu
84 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Appendix B Single Line DiagramsFigure 19 - 6012M Automatic Bypass Version 1 (without
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 85Single Line Diagrams Appendix BFigure 20 - 6012M Automatic Bypass Version 2 (with Is
86 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Appendix B Single Line DiagramsFigure 21 - 6012M Manual BypassQFInput Circuit Breake
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 87Appendix CSpecial Function Parameter SettingsOverviewTable 12 on page 68 outlines sp
88 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Appendix C Special Function Parameter SettingsSwitch Control SourcesRelevant paramet
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 89Special Function Parameter Settings Appendix CAnalog Output Display Parameter Settin
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 9PrefaceGeneral PrecautionsAdditional ResourcesThese documents contain additional info
90 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Appendix C Special Function Parameter SettingsSpeed Command FunctionsSet Frequency C
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 91Special Function Parameter Settings Appendix CFrequency Amplitude LimitRelevant para
92 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Appendix C Special Function Parameter SettingsSpeed Reference FunctionsV/F Curve Set
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 93Special Function Parameter Settings Appendix CAnalog InputRelevant parameter: P205,
94 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Appendix C Special Function Parameter SettingsSome parameters must be changed based
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 95IndexAAnalog Input 93CCabinet PlatesPre-Commissioning Sealing 29Commissioning 31Cont
96 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014IndexMechanical Inspection 21Interconnection Review 20Checklist 20Software 15Test Eq