Publication 4100-UM052B-EN-P - October 2001
Installation & Hook-Up 27
Figure 11 Wiring diagram for connecting a Servo Amplifier
to the Control Connector
Power Supply Connector
The power supply connector is used to connect power to the AEC.
There is one power input connector for the AEC. The input power is
used to operate the AEC and attached transducers.
The AEC operates within the voltage range of 18-36V DC. The power
source must be able to supply 21W of power continuously.
8
7
6
5
4
3
2
1
Plug A
Plug B
Reference +
Shield
Reference -
To Servo Amplifier
IMPORTANT
Anchor the cable so that no more than 2 feet of cable is
left unsupported. The excessive weight of an unanchored
cable could pull the plug out of the connector.