200 Publication 2711-UM014G-EN-P - September 2008
Chapter 12 Terminal Connections
Connecting to an SLC, CompactLogix, MicroLogix Controller
(Point-to-point)
This section shows how to connect a CompactLogix, MicroLogix
1500LRP, or SLC controller (SLC 5/03, SLC 5/04, or SLC 5/05) to the
RS-232 PanelView terminal for point-to-point (DH-485)
communication. On terminals with two ports, use the RS-232
communication port.
For the SLC, CompactLogix or MicroLogix 1500LRP controller, use one
of these cables:
5 m (16.4 ft) Cat. No. 2711-NC13
10 m (32.7 ft) Cat. No. 2711-NC14
3 m (10 ft) Cat. No. 2706-NC13
For the MicroLogix 1000, MicroLogix 1200, or MicroLogix 1500LSP
controller, use one of these cables:
5 m (16.4 ft) Cat. No. 2711-NC21
15 m (49 ft) Cat. No. 2711-NC22
To PanelView Terminal 9-pin,
Male, D-Shell Connector
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
Pin #Pin #
To SLC 5/03, 5/04, 5/05, Compact
Logix or MicroLogix 1500LRP Channel
0 Port 9-pin, Male, D-Shell Connector
Required
Data Out (TXD)
Data In (RXD)
Signal Common
Data Out (TXD)
Data In (RXD)
Signal Common
Cable, Cat. No. 2711-NC13
Cable, Cat. No. 2711-NC14
Cable, Cat. No. 2706-NC13
PanelView 1000 Terminal
SLC 5/03, 5/04, 5/05
1
5
9
6
6
9
5
1
CompactLogix
MicroLogix 1500LRP
IMPORTANT
You must configure the Channel 0 Port of the SLC 5/03,
SLC 5/04, SLC 5/05 controller for DH-485 communication using
the Resolutes 500 or AI500 software.
MicroLogix 1000, 1200, 1500LSP
PanelView 1000 Terminal
Cable, Cat. No. 2711-NC21
Cable, Cat. No. 2711-NC22
(null modem not required)