Chapter 5
Maintenance and Troubleshooting
5–6
Since the Push Button Module is part of an integrated system, you must
evaluate the entire system when a fault is detected. Start your
troubleshooting by asking these basic questions:
• Is the source power to the Push Button Module present?
• Do you have a communications light? If not, check your twin-axial cable
wiring. The blue and clear wires may be interchanged.
• Is the rack address set properly? Refer to Chapter 2.
• Are the baud rates of the Push Button Module and the Scanner Module
the same? Refer to Chapter 2.
• Is the Push Button Module the last in a series of modules, and has it been
identified as the last rack? Refer to Chapter 2.
• Is the communication connector securely plugged in at both the Push
Button Module end and the Scanner Module end?
• Have you changed the settings of any of the DIP switches? New DIP
switch settings are not acknowledged until power is cycled. Refer to
Chapter 2.
• On modules with a switch selectable power supply, is the 120/240 AC
voltage switch position correct?
• If applicable, is the fuse properly installed and in working order?
Basic Troubleshooting
Questions