Rockwell Automation Publication 520COM-UM001A-EN-E - April 2013 105
DeviceNet Objects Appendix C
Class Attributes
Instance Attributes
Attribute ID Access Rule Description
1 Read Revision
2 Read Maximum Instance
3ReadNumber of Instance
100 Read/Write Timeout
Attribute ID Access Rule Name Data Type Description
1 Get Bad Flag BOOL If set to 1, then attribute 4 may contain invalid data.
0 = good
1 = bad
2 Get Direction BOOL Direction of data transfer
0 = Produce Register (drive to network)
1 = Consume Register (network to drive)
3 Get Size UINT Size of register data in bits
4 Conditional
(1)
(1) The access rule of Set is optional if attribute 2, Direction = 1. If Direction = 0, the access rule is Get.
Data Array of Bits Data to be transferred
IMPORTANT
Setting the “Data” instance attribute can be done only when the Control
Timeout (class attribute 100) has been set to a non-zero value.