Installing the Adapter 2-5
4. Fold the Internal Interface cable behind the adapter and mount the
adapter on the drive using the four captive screws to secure and
ground it to the drive.
Important: On a PowerFlex 70 drive, tighten the screw in the lower
right hole to ground the adapter.
On a PowerFlex 700 drive, tighten the screw in the lower
left hole to ground the adapter.
Figure 2.3 Mounting the Adapter
Adapter
Drive
PowerFlex 70 Drive
Adapter mounts in drive.
PowerFlex 700 Drive (0 - 1 Frames)
Adapter mounts on door.
PowerFlex 700 Drive (2 Frame & Larger)
Adapter mounts in drive.
Internal Interface cable folded
behind the adapter and in front of drive.
20COMM-UM007A-EN-P.book Page 5 Tuesday, January 22, 2002 10:52 AM