Publication 1794-UM064B-EN-P - May 2014
88 Configure the Adapter for Master/Slave Communication
The maximum size of this identifier area is 17 bytes. If no FLEX I/O modules are
installed in the upper slots, the length may be less. Consistency must be over a
word.
Refer to your configuration tool publications for information on how and where
to enter this data.
Refer to your configuration tool publications for information on how and where
to enter this data.
Check Configuration Example
Check Configuration Message when used with Send Parameter Auto Configure or
Condensed Format (Length 10 bytes)
Name Identifier Byte Description
Octet 1: 50h Input Status Word (input – 1 word)
Octet 2: 60h Output Status Word (output – 1 word)
Octet 3: 51h Slot 1, input module 2 words
Octet 4: 60h Slot 1, output module 1 word
Octet 5: 00h Slot 2, input module empty
Octet 6: 60h Slot 2, output module 1 word
Octet 7: 57h Slot 3, input module 8 words
Octet 8: 60h Slot 3, output module 1 word
Octet 9: 50h Slot 4, input module empty
Octet 10: 65h Slot 4, output module 6 words
I/O sizes configured: 22 input bytes, 20 output bytes
Check Configuration Example
Check Configuration Message when used with Send Parameter Full Format
(Length 10 bytes)
Name Identifier Byte Description
Octet 1: 50h Status Word (input – 1 word)
Octet 2: 60h Output Status Word (output – 1 word)
Octet 3: 51h Slot 1, input module 2 words
Octet 4: 00h Slot 1, output module 1 word
Octet 5: 00h Slot 2, input module empty
Octet 6: 60h Slot 2, output module 1 word
Octet 7: 57h Slot 3, input module 8 words
Octet 8: 00h Slot 3, output module 1 word
Octet 9: 00h Slot 4, input module empty
Octet 10: 63h Slot 4, output module 6 words
I/O sizes configured: 22 input bytes, 12 output bytes