ArmorBlock-LP 8 Output Module 9
Publication
1792-5.7 – December 1997
30197–M
NS = Network Status Indicator
Output Short
Circuit Indicator
U
S
= Output Power
Supply Status Indicator
U
L
= Module Power Supply
Status Indicator
A = Output
Status Indicators
MS = Module Status
Indicator
Output
Connector
OUT
1
2
34
5
6
7
8
A
A
A
A
A
A
A
A
OUT
Network
Status Indicator (NS)
Indication Status
Flashing Green
On-line, not connected
Solid Green
Link OK, on-line connected
Flashing Red
At least 1 I/O connection is in the timed-out state
Solid Red
Incorrect baud rate, or a duplicate Mac ID exists
Module Status Indicator (MS)
Indication Status
OFF
No power
, or no network access
Flashing Green/OFF
On-line but not connected
Solid Green
On-line, link okay
, connected
Flashing Red
Recoverable fault
Solid Red
Critical failure
Output Short Circuit Indicator
Indication Status
OFF
No shorted outputs
Solid Red
Shorted output
Output I/O Status Indicator (1A thru 8A)
Indication Status
OFF
Output is of
f
Yellow
Output is on
Module and Output Power Supply Status Indicators U
S
and U
L
Indication Status
OFF
Power supply is not functioning correctly
Green
Power Supply is operating
Zobrazit stránku 8