ArmorBlock-LP 8 Output Module10
Publication
1792-5.7 – December 1997
Specifications
8 Output Module – Cat. No. 1792-OB8PLP
Output Power Supply Note: In order to comply with CE Low Voltage
Directives, you must use a Safety Extra Low Voltage
(SELV) or a Protected Extra Low Voltage (PELV)
power supply to power the outputs of this module.
Output Specifications
Outputs per Block 8 Sourcing Outputs – labeled 1A through 8A
Output Voltage Range 19–30V dc
On-state Current Maximum 2.0A per output at 60
o
C
On-state Voltage Maximum 3.0V dc at rated current
Module Current (all outputs
on)
12.0A per module
Off-state Leakage Current 1.5mA maximum per output
Surge Current Maximum 4.0A for 10ms, repeatable every 2s
Indicators Network Status – red/green
Module Status – red/green
Output Status – Yellow
Output Fault – Red
Module Power Supply Status – green
Communication Rate in Baud 125k, 250k, 500k software selectable
Specifications continued on next page.