Message Formats
Appendix A
A26
Diagnostic Read
You use this command to read up to 244 bytes of data from the PROM or
RAM of the station interface module. You can use it to read the modules
diagnostic timers and counters. Use the diagnostic status command to
obtain the starting address of the diagnostic counters.
Command Format:
FNC
DLE
SRC
STX DST C
06
S
TNS
MD
TS
TNS
DLE ETX
BCC
01
SIZEADDR
Reply Format:
DLE
C
S
TNS
MD
TS
TNS
STX
DLE ETX
BCC
DATA - Max of 244 bytes
DST
SRC
46
Diagnostic Status
You use this command to read a block of status information from the
station interface module. The reply to this command contains the status
information in its DATA field.
Command Format:
FNC
DLE
SRC
STX DST C
06
S
TNS
MD
TS
TNS
DLE ETX
BCC
03
Reply Format:
DLE
C
S
TNS
MD
TS
TNS
STX
DLE ETX
BCC
DATA - Max of 244 bytes
DST
SRC
46
The status information varies with the type of station interface module.
Table A.B describes this status DATA for 1775–KA modules.