DC (24V) Isolated Output Module 13
Publication 1771ĆIN057B-EN-P - November 2002
Outputs per Module 16
Module Location 1771ĆA1B thru Ć A1B or later I/O Chassis
Voltage Rating 10 to 32V dc
Maximum Output Current 2.0A per output; 32.0A maximum per module at 0-45
o
C;
Derate linearly to 1.5A per output, 24A maximum per module at 60
o
C-
See derating curve.
Minimum Output Current 5mA
OnĆstate Voltage Drop (maximum) 0.34A per output at 2A
OffĆstate Leakage Current
(maximum)
0.5mA per output @ 32V dc, 25
o
C
Surge Current (maximum) 4A for 10ms per output., repeatable every 2 sec.
Power Rating 0.68W per output (maximum) @ 2A
Output Signal Delay Off to On
On to Off
100μs (max);
300μs (max)
Power Dissipation 13.0 Watts (max); 2.0 Watts (min)
Thermal Dissipation 44.3 BTU/hr (max); 6.8 BTU/hr (min)
Adjacent Slot Power Dissipation 10.0 Watts
Backplane Current 400mA maximum
Isolation Voltage Tested for 1s at 1500V channelĆtoĆchannel,
1500V channel to backplane
Maximum Cable Length 1000 ft (304.8 m)
Conductors Wire Size
Category
14 to 22 gauge (2.5mm
2
to 0.25mm
2
) stranded or solid copper wire rated
at 60
o
C or greater
1, 2
3/64 inch insulation maximum
2
3
Environmental Conditions
Operating
Temperature
IEC 60068-2-1 (Test Ad, Operating Cold)
IEC 60068-2-2 (Test Bd, Operating Dry Heat)
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
32 to 140°F(0
o
to 60
o
C) See derating curve.
Storage Temperature IEC 60068-2-1 (Test Ab, Unpackaged, Nonoperating Cold)
IEC 60068-2-2 (Test Bb, Unpackaged, Nonoperating Dry Heat)
IEC 60068-2-14 (Test Na, Unpackaged, Nonoperating Thermal Shock)
-40 to 185°F (-40 to 85
o
C)
Relative Humidity IEC 60068-2-30 (Test Db, Unpackaged, Nonoperating Damp Heat)
5 to 95%, noncondensing
Shock
Operating
Nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30g
50g
Vibration IEC 60068-2-6 (Test Fc, Operating)
2g @ 10-500Hz
ESD Immunity IEC 61000-4-2
4kV indirect discharges
Radiated RF Immunity IEC 61000-4-3
10V/m, with 1kHz sine-wave 80% AM from 30MHz to 1000MHz
EFT/B Immunity IEC 61000-4-4
+
1kV @ 5kHz on signal ports
Surge Transient Immunity IEC 61000-4-5
+
1kV line-line (DM) and +2kV line-earth (CM) on signal ports