Rockwell-automation 1770-KF2 Data Highway or Highway Plus Interface Mo Uživatelský manuál Strana 104

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 235
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 103
Message Packet Formats
Chapter 5
5-25
Physical Write
This command writes bytes of data into the PC data table or program
memory. Use this command to download a computer file into PLC
memory.
Use the SIZE field to specify the number of bytes to be written. To
specify a number of PC words, SIZE should be an even value because PC
words are two bytes long.
Command
Format:
Reply Format:
TNSSTSCMD
03
SRCDST
TNSSTSCMD
43
SRCDST
ADDR
DATA
— Max. of 242 Bytes
PLC-2 Commands
PLC-2 stations can execute all of the commands in the basic command
set. They can also execute the following commands, which apply only to
PLC-2 Family controllers:
Enter Download Mode
Enter Upload Mode
Exit Download/Upload Mode
Physical Read
Physical Write
Set Data Table Size
The above commands are privileged. This means that only a computer
can initiate them. Their primary use is for uploading and downloading
PLC-2 memory.
Zobrazit stránku 103
1 2 ... 99 100 101 102 103 104 105 106 107 108 109 ... 234 235

Komentáře k této Příručce

Žádné komentáře