12–10 Uploading and Downloading with A-B Processors
Publication
17706.5.16 - October 1996
Procedure 2
1. Verify the processor type using diagnostic status. (For more on
diagnostic status, see page 7–6.)
2. Place the PLC-5 processor in Program or Remote
program mode using set CPU mode or the keyswitch on the front
of the processor. (For more on set CPU mode,
see page 7–26.)
3. Place the PLC-5 processor in Download mode using download all
request. (For more on download all request, see page 7–7.)
4. Send PLC-5 memory information to the appropriate physical
addresses in PLC-5 memory using write bytes physical with the
information stored in the archive file from the upload procedure.
(For more on write bytes physical, see page 7–35.)
5. Exit Download mode using download complete. (For more on
download complete, see page 7–7.)
Downloading to an SLC 500 Processor
If you have this SLC processor Then
SLC 500, SLC 5/01, or SLC 5/02 Follow procedure 1 on page 12-11