3. Tighten the terminal screw making sure the pressure plate secures the
wire. Recommended torque when tightening terminal screws is 0.68
N•m (6 in•lb).
Wire Size and Terminal Screw Torque
Each terminal accepts up to two wires with the following restrictions.
I/O Memory Mapping
Output Data File
For each module, slot x, words 0…7 in the output data file contain the channel
0 …7 output data. Word 8 is used to unlatch any condition that has been latched.
Refer to the Compact I/O Analog Modules User Manual, publication
1769-UM002
, for additional details.
TIP
If you need to remove the finger-safe cover, insert a screw driver into one
of the square, wiring holes and gently pry the cover off. If you wire the
terminal block with the finger-safe cover removed, you will not be able to
put the cover back on the terminal block because the wires will obstruct
the cover.
Wire Type Wire Size Terminal Screw
Torque
Retaining Screw
Torque
Solid Cu-90 °C (194 °F) #14…#22 AWG 0.68 N•m
(6 lb•in)
0.46 N•m
(4.1 lb•in)
Stranded Cu-90 °C (194 °F) #16…#22 AWG 0.68 N•m
(6 lb•in)
0.46 N•m
(4.1 lb•in)
IMPORTANT
If you are using RSLogix 5000 software, version 15, please refer to
RSLogix 5000 Controller Tags
on page 22
Word
Bit Position
1514131211109876543210
0 SGN Analog Output Data Channel 0