16 Compact™ 1769-IF4 (Series B or Later) Analog Input Module
Publication 1769-IN048A-EN-P
Configuration Data File
The manipulation of the bits from this file is normally done with
programming software (e.g. RSLogix 500, RSNetworx for DeviceNet, etc.)
during initial configuration of the system. In that case, graphical screens are
provided by the programmer to simplify configuration. However, some
systems, like the 1769-ADN DeviceNet Adapter, also allow the bits to be
altered as part of the control program, using communication rungs. In that
case, it is necessary to understand the bit arrangement. Refer to the
Compact™ Analog I/O User Manual, publication number
1769-UM002A-EN-P for additional details.
Words 0 to 3 of the configuration file allow you to change the parameters
of each channel independently. For example, word 0 corresponds to
channel 0.
Define To Select Make these bit settings
151413 12111098 4-7 3210
Input Filter
Selection/
-3 dB
Frequency
60 Hz/15.7 Hz
Not Used
0000
50 Hz/13.1 Hz
0001
Not Used
0010
250 Hz/65.5 Hz
0011
500 Hz/131Hz
0100
Spare
(1)
(1) An attempt to write any non-valid (spare) bit configuration into any selection field results in a module
configuration error.
Input Type/
Range
-10 to +10V dc
0000
0 to 5V dc
0001
0 to 10V dc
0010
4 to 20 mA
0011
1 to 5V dc
0100
0 to 20 mA
0101
Spare
(1)
Input Data
Format
Raw/Proportional
Data
000
Engineering Units
001
Scaled-for-PID
010
Percent Range
011
Spare
(1)
Enable
Channel
Enabled
1
Disabled
0
Komentáře k této Příručce