Rockwell Automation Publication 1769-UM006E-EN-P - July 2013 103
Module Configuration, Output, and Input Data Chapter 4
Invalid Counter Assigned to Range (InvalidCtrAssignToRange12 through
InvalidCtrAssignToRange15)
InvalidCtrAssignToRange12 is set when the indicated range in the output array
refers to a non-existent counter.
It is set (1) when Range12To15[n].ToThisCounter > NumberOfCounters.
It is cleared (0) when Range12To15[n].ToThisCounter
NumberOfCounters.
When this error occurs, the entire output array is rejected until a valid
configuration is detected.
Invalid Range Limit (InvalidRangeLimit12 through InvalidRangeLimit15)
This bit is set when the range limits are invalid according to the limitations
indicated in Range12To15[n].HiLimOrDirWr and Range12To15[n].LowLimit
in the output array.
1 = Range limits are invalid.
0 = no error
When this error occurs, the entire output array is rejected until a valid
configuration is detected.
Range Active (RangeActive.0 through RangeActive.15)
This word reflects the status of all of the ranges. When a count or rate meets the
criteria programmed for a given range, the range is active.
1 = active
0 = inactive/false
Input Array Word 3 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Range Active RangeActive.0 through RangeActive.15
Input Array Word 3 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Range Active RA3 RA2 RA1 RA0
TIP
When the range is enabled and active, the output mask for that range is
applied.