Rockwell-automation 1757-SWKIT400 Getting Started with ProcessLogix R4 Uživatelský manuál Strana 16

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 24
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 15
16 Getting Started with ProcessLogix R400.0
Publication 1757-QS040A-EN-P - October 2001
7. Locate the Labx I/O modules in the CEE0101 folder of the Project tab.
8. Load the IOMs by doing the following:
a. Select all of the IOMs in the I/O list area.
b. Click the green down arrow (load) in the toolbar.
The Load dialog box appears.
c. Verify that the I/O modules are all checked and click OK.
The assigned I/O modules appear under their CPM in the Monitor and
Project tabs.
TIP
To locate the IOMs, you may need to expand the CEE and I/O
branches of the tree in the Project tab.
ATTENTION
!
Load only the I/O modules that physically exist in the chassis.
TIP
In Monitoring tab:
blue indicates “inactive,”
green indicates “active and OK.”
red indicates “active and failed.”
Double-click the I/O module in the Monitoring tab to see
connection status on the Module Configuration tab.
Zobrazit stránku 15
1 2 ... 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Komentáře k této Příručce

Žádné komentáře